7-31
Chapter 7. PARAMETER SETUP
Setting
0: Reverse action (heat)
1: Direct action (cool)
[Note]
On heat/cool models when setup data
C44 setting is 0, “- - - -”
is displayed and setting is not possible.
On other models, external switch input can invert direct/reverse
action on the setting of
C01.
0: °C
1: °F
[Note]
On PV2 channel models when the input 1 range type is linear,
“- - - -” is displayed and setting is not possible.
0 to 73
0 to 20: Thermocouple
32 to 40, 48 to 56: Resistance temperature detector
64 to 73: Linear (DC current, DC voltage)
[Note]
Refer to the input 1 range table. Operation according to a
setting not listed in this table is not fixed.
0 to 3
[Note]
When the input 1 range type is non-linear, “- - - -” is displayed
and setting is not possible.
When the input 1 range type is changed from non-linear to
linear, the original non-linear range values remain.
-1999 to +9999U
[Note]
When the input 1 range type is non-linear, “- - - -” is displayed
and setting is not possible.
When the input 1 range type is changed from non-linear to
linear, the original non-linear range values remain.
The relationship between the analog inputs and readout values
can be inverted by inverting the upper and lower limit values.
0.0 to 10.0% (ratio to input range)
[Note]
0.0 disables square root extraction.
When the input 1 range type is non-linear, “- - - -” is displayed
and setting is not possible.
0: Disabled
1: Enabled
[Note]
Table data setting (
A, b) is used for the linearization table.
-1999 to upper limit U
[Note]
Changing the input 1 range has no effect on the range.
However, note that a general reset sets the range to the 0%FS
value of the input 1 range.
Lower limit to +9999U
[Note]
Changing the input 1 range has no effect on the range.
However, note that a general reset sets the range to the
100%FS value of the input 1 range.
0: OFF (PID set segment designation)
1: ON
[Note]
When set to 1, the PID set items in the program are invalid.
The switching point for auto-switching is set in variable
parameters (
CP.11 to CP.17).
0: OFF
1: ON
No. Item Code
Item
1
C01
Control action (CH1)
2
C02
Input 1 temperature unit
3
C03
Input 1 range type
4
C04
Input 1 range decimal
point position
5
C05
Input 1 range lower limit
(0%)
6
C06
Input 1 range upper limit
(100%)
7
C07
Input 1 root extraction
dropout
8
C08
Input 1 linearization table
approximation
9
C09
SP1 lower limit
10
C10
SP1 upper limit
11
C11
PID set auto-switching
(CH1)
12
C12
MV1 setting at input 1
over-range
Factory
Setting
0
0
0
Not
fixed
Not
fixed
Not
fixed
0.0
0
0%FS
100%FS
0
0
User
Setting
■
Setup data settings “
SEt
”