7-34
Chapter 7. PARAMETER SETUP
Setting
-10 to +110%
[Note]
When the model is not a heat/cool model, and setup data
C44 is set to
0 on a heat/cool model, “- - - -” is displayed and setting is not possible.
Input 2 channel model
0: MV2 output (controller function)
1: SP2 output (programmer function)
2: SP2 output (programmer function)
Temperature/humidity operation model
0: MV2 output (controller function)
1: SP2 output (programmer function)
2: SPw output (SPw programmer function)
[Note]
“- - - -” is displayed and setting is not possible in the following
instances:
• 0D output:
C44 setting is 0 and C76 setting is 0
• 5G output:
C44 setting is 1 and C75 setting is 0
C44 setting is 0 and C76 setting is 0
• 2G/3D/5K output:
C44 setting is 0 and C77 setting is 0
On input 2 channel models, settings 1 and 2 mean the same.
-1999 to +9999U
[Note]
When
C41 setting is “- - - -” or 0, “- - - -” is displayed and setting is not
possible.
The relationship between the analog outputs and SP2 and SPw can
be inverted by inverting the upper and lower limit values.
0: MV1/2 switching OFF
1: MV1/2 switching ON
[Note]
• On heat/cool and non-2G output models
When set to 0, MV1 is switched to output 1, and MV2 is switched to
output 2.
When set to 1, MV1 is switched to output 2, and MV2 is switched to
output 1.
• On heat/cool and 2G output models
When set to 0, MV1 is switched to output 1 + output 2, and MV2 is
switched to output 3.
When set to 1, MV1 is switched to output 3, and MV2 is switched to
output 1 + output 2.
0: 3-position control disabled
1: 3-position control enabled
[Note]
On models not supporting 3D output, “- - - -” is displayed and setting is
not possible.
[Note]
“- - - -” is displayed and setting is not possible.
0: PV1
6: Deviation 2
1: SP1
7: MV2
2: Deviation 1
8: MFB
3: MV1
9: PVw
4: PV2
10: SPw
5: SP2
11: NOP
[Note]
When auxiliary output is not supported, “- - - -” is displayed and setting
is not possible.
Output is fixed to 4 mA or 0 mA in the following instances:
• When set to NOP
• When set to MFB on non-2G output models
• When set to PVw and SPw on input 2 channel models
• When set to SP or deviation and output is in the READY mode
No. Item Code
Item
40
C40
MV (cool) in
READY mode
(MV2 cool
output)
41
C41
Main output type
(CH2)
42
C42
SP2 main output
lower limit
(4 mA)
43
C43
SP2 main output
upper limit
(20 mA)
44
C44
MV1/2 switching
45
C45
3-position control
46
C46
Unused
47
C57
Unused
48
C48
Unused
49
C49
Auxiliary output
type
Factory
Setting
0
0
0U
1000U
0
0
—
—
—
0
User
Setting