![Yamatake DigitroniK DCP32 User Manual Download Page 146](http://html.mh-extra.com/html/yamatake/digitronik-dcp32/digitronik-dcp32_user-manual_905225146.webp)
7-46
Chapter 7. PARAMETER SETUP
■
Description of table data settings
●
t-A.1 to t-A.b
●
t-b.1 to t-b.b
• These settings are for the A-axis (input) and B-axis (output) settings of input 1
linearization table approximation.
• Both ends of the linearization table are fixed at -2000U, -2000U and
10000U,10000U. The linearization table is formed by connecting 11 points of
table data settings between the two ends.
• Table data is set not by percentages but directly by engineering unit. When the
range type is set to linear, set scaled values.
• Points on the broken-line, An and Bn, must be set so that they increase in the
following way (A1, B1) = (0, 0), (A2, B2) = (100, 100) and so forth. If set
points break this relationship, the point in conflict must be excluded to create
the linearization table.
• When two equal points such as A1 and A2 are set for the A-axis, B1 shall be
taken as the output value.
●
t-C.1- to t-C.b
●
t-d.1- to t-d.b
•
These settings are for the C-axis (input) and D-axis (output) settings of input 2
linearization table approximation.
• In the above figures, the functions of the A-and B-axes are transferred to the C-
and D-axes.
1
2
3
4
5
6
7
8
9
10
11
Fixed value
(10000, 10000)
Fixed value
(-2000, -2000)
B-axis (output)
A-axis (input)
B-axis
A-axis
(A , B )
2
2
(A , B )
3
3
(A , B )
1
1
(A , B )
2
2
(A , B )
3
3
(A , B )
1
1
B-axis
A-axis
This point is excluded
B-axis
A-axis
(A , B )
2
2
(A , B )
1
1