![Yamatake DigitroniK DCP32 User Manual Download Page 177](http://html.mh-extra.com/html/yamatake/digitronik-dcp32/digitronik-dcp32_user-manual_905225177.webp)
9-9
Chapter 9. MAINTENANCE & TROUBLESHOOTING
●
Event items cannot be displayed by Repeatedly pressing the
↑
key and the
↓
key.
●
Repeatedly pressing the
↑
key and the
↓
key does not display time events.
●
Repeatedly pressing the
↑
key and the
↓
key does not display PID set items (CH1) and PID
set items (CH2).
●
Repeatedly pressing the
↑
key and the
↓
key does not display G.Soak items (CH1) and
G.Soak items (CH2).
●
Repeatedly pressing the
↑
key and the
↓
key does not display PV start items, cycle items
and pattern link items.
●
Pressing the FUNC key + the ENT key does not confirm insertion/deletion of segments.
Remedy
Set event type (
Et1, Et2, Et3) in event configuration data to one of
1 to 11 or 50.
Set setup data
C68 setting to 0.
Cause
Event type is controller status event.
Programming items are set to “display OFF”.
Remedy
Change event configuration data
tt setting and assign to time
event.
Select a model that supports time events (option).
Set setup data
C69 setting to 0.
Cause
Time event is assigned to segment No. event.
This model does not support time events.
Programming items are set to “display OFF”.
Remedy
Set setup data
C11 setting or C34 setting to 0.
Set setup data
C18 setting or C41 setting to 0.
Set setup data
C45 setting to 0 and switch to PID control from 3-
position control.
Set setup data
C70 setting to 0.
Cause
PID set auto-switching is set to ON.
The DCP32 is set to programmer function by current
output.
3-position control is selected on a 3D output model.
Programming items are set to “display OFF”.
Remedy
Set setup data
C70 setting to 0.
Cause
Programming items are set to “display OFF”.
Remedy
Set setup data
C71 setting to 0.
Cause
Programming items are set to “display OFF”.
Remedy
Set program parameter
PrtC setting to 0.
Reset the DCP32 (PROG + RUN/HOLD key) to set it to the
READY mode.
Move to pattern item on programming map.
Either move to already set up segment, or set up segment.
Cause
The program setup cannot be changed.
The program being set up is being operated (RUN,
HOLD, FAST, END).
Not pattern item on programming map
Pattern item of non-set segment on programming map