5-9
Chapter 5. FUNCTIONS
■
G.Soak (guarantee soak)
G.Soak ON/OFF and G.Soak width can be set
for each segment. The G.Soak time can also be
set by the variable parameter
gs.t
item. The
G.Soak function ensures a segment execution
time with PV close to SP. G.Soak functions not
only in soak segments but also in ramp
segments.
At the segment start point, PV and SP are
compared, and the absolute value of the
resulting deviation continues for the G.Soak
time or longer. When the absolute value is
smaller than the G.Soak width, operation of that
segment is started.
The DCP32 is in the G.Soak standby state until
this condition is satisfied, and the line lamp on
the left side of the profile display blinks. The
operation state is the same as HOLD at the
segment start point (time is set to 0).
If G.Soak standby is canceled on both channels
when G.Soak is set to ON on channels CH1 and
CH2, operation of that segment starts.
However, note that in the FAST mode, the
DCP32 does not enter the G.Soak standby state
even if G.Soak is set to ON. The G.Soak
standby state can also be canceled by external
switch output. The following cancel conditions
can be used for both CH1 and CH2, and
selected by the setup date
C52
to
C54
settings.
1
G.Soak cancel when external switch input
contact is ON or PV satisfies the G.Soak
cancel conditions
2
G.Soak cancel when external switch input
contact is ON and PV satisfies the G.Soak
cancel conditions
Time
SP
G.Soak width
G.Soak width
SP
PV
Segment
set time
Segment
execution time
G.Soak standby time
Time count start
G.Soak time