E5 Series High Performance Universal Inverter User’s Manual
Chapter 4 Operation Panel
39
4.7 Operation Panel Display and Key Operation
4.7.T Classification of Display Status
There are 8 types of display status of operation panel:
SN
Status
Meaning
T
Display parameters in stop status
Press >> key to switch the displayed parameters
PT.03 can be used to set the displayed parameters
T
Display parameters in running status
Press >> key to switch the displayed parameters
PT.0T can be used to set the displayed parameters
3
Fault and alarm display status
In other 7 kinds of display status, if there is any fault happens, directly enter
this status
4
Display status of first level menu
When the keys are not locked, in status of SNT, SNT, SN3 and SN7, press
PRG to enter
5
Display status of second level menu
In the display status of first level menu, press PRG to enter
6
Password verification status
If password protection is enabled, press PRG to enter in the display status of
first level menu
7
Password modification status
In the display status of stop and running parameters, press
∧
and
∨
to enter
8
Information prompt status
See 4.4.5 for identifying the LED display characters
4.7.T Display Status and Operation Process
>> key
In the display status of first level menu, press >> key to select the edit bit of parameter PX.YZ.
In second level menu or password verification status, press >> key to select the data edit bit.
Display status auto changed
If no key is pressed for 30s, the screen automatically returns to the display status of parameter in stop
status or running status.
If no key is pressed for T minute, clear menu edit status of PX.YZ to return to P0.00.
If there is password setting or key locking setting, and if no key is pressed for 5 minutes, the password
protection or locking status will be activated automatically.
Display status and operation procedure
Figure 4−5 Display status and operation procedure
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...