E5 Series High Performance Universal Inverter User’s Manual
Chapter 6 Parameter Descriptions
117
This function realized energy saving control for fan or pump.
When the actual running frequency lower than the sleep frequency setting(H0.06), and last longer than
the delay time set in H0.07, the frequency decelerate to 0 Hz.
When the actual pressure feedback lower than wake up pressure percentage (H0.08), and last longer
than the delay time set in H0.09, re
−
enter the PID regulator, the motor start running.
Note:
In sleep status, the operation panel display
“
−SL−
”
Sleep delay time H0.07 setting should be longer than acceleration time
Wake up pressure percentage (H0.08) is percentage of pressure setting
Pressure setting channel is determine by H0.04
The function realized auto switch acceleration time and deceleration time during acceleration and
deceleration.
When the frequency reference lower than H0.TT, the inverter will automatically switch to acceleration
and deceleration time define by H0.TT.
For example, if running frequency 0 to T0Hz the acceleration and deceleration time is T0.0s. And running
frequency is T0.00Hz to maximum frequency acceleration and deceleration time is 6.0s, the parameters
should be set: H0.TT=T0.00Hz,H0.TT=T, P0.08=6.0s, P0.09=6.0s, P4.09=T0.0s, P4.T0=T0.0s.
When H0.30 is set to 0, sleep and wake up mode according the parameter of H0.00.
When H0.30 is set to T, sleep and wake up mode according the parameter of H0.3T to H0.34.
These parameters realized energy saving for fan or pump.
When PID is set to positive function (setting P8.09 to 0):
If pressure feedback exceeds sleep pressure setting (H0.3T), and last longer than sleep delay time
(H0.34), the frequency decelerate to 0 Hz.
If pressure feedback lower than wake up pressure setting (H0.3T), and last longer than wake up
delay time (H0.33), re
−
enter the PID regulator and acceleration from 0 Hz.
0.0 ~ 3600.0 s
(
30.0s
)
0 ~ 3
(
T
)
Acceleration time and deceleration time automatically switch
H0.TT
0.00 ~ 300.00 Hz
(
0.00Hz
)
Frequency of auto switch acceleration time and deceleration time
H0.TT
Exit wake-up delay time
H0.09
0.0 ~ T00.0 %
(
50%
)
Wake up pressure percentage
H0.08
0.0 ~ 3600.0 s
(
60.0s
)
Sleep delay time
H0.07
0.00 ~ 300.00 Hz
(
30.00Hz
)
Sleep frequency setting
H0.06
H0.30
Sleep and wake up mode selection
0 ~ T
(
0
)
H0.3T
Wake up pressure setting
0.00 ~ T0.00V
(
0.00V
)
H0.3T
Sleep pressure setting
0.00 ~ T0.00V
(
0.00V
)
H0.33
Wake up delay time
0.0 ~ 3600.0s
(
0.0s
)
H0.34
Sleep delay time
0.0 ~ 3600.0s
(
0.0s
)
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...