E5 Series High Performance Universal Inverter User’s Manual
32
Chapter 4 Operation Panel
Table 4−1 Multi−function
M
key function selection and the meanings of MULTI indicator
Value
setting
(P2.01)
Function
Descriptions
Meanings of MULTI
indicator
0
No function
M key is defined as no function.
Normally Off: No function
T
JOG
Used as JOG operation key and is only
enabled when run command is given via
operation panel
In stop status, press M key to enter jog
operation status, and release this key to stop
On: Press M
Off: Release M to finish the
jog operation
T
Emergency stop T
(stop in shortest time)
Press M key, inverter will stop in shortest time
On: Press M
Off: Release M
3
Emergency stop T
(coast to stop)
Press M key, inverter will coast to stop
On: Press M
Off: Release M
4
Switchover of run
command channel
Press M key to switch the run command
channel:
Operation panel→Terminal → Communication
→ Operation panel.
During switchover time, there is a 5−second
response time limit and the change is
canceled automatically after 5−second time is
exceeded. Within 5s, press PRG key to
confirm the change. MON indicator indicates
the run command channel
On: Press M
Off: M key has been released
for more than 5s or PRG
key has been used to
confirm the changing of
the run command source
5
Switchover of
parameters displayed
mode FAStTbASE
Press M key to switch between FASt and
bASE parameters displayed mode panel
should prompt as FASt and bASE
On: FASt, fast parameters
displayed mode
Off: bASE, basic parameters
displayed mode
6
Switchover of
parameters displayed
mode ndFtTbASE
Press M key to switch between ndFt and bASE
parameters displayed mode, the indications on
the operation panel are ndFt and bASE
respectively
On: ndFt,non−factory setting
parameters displayed
mode
Off: bASE, basic parameters
displayed mode
7
Switchover of
parameters displayed
mode LAStTbASE
Press M key to switch between LASt and
bASE parameters displayed mode, the
indications on the operation panel are LASt
and bASE respectively
On: LASt, last change T0
parameters
displayed
mode
Off: bASE, basic parameters
displayed mode
8
Switchover of
parameters displayed
mode
bASE→FASt→ndFt→LASt→bASE
On: non−bASE basic
parameters displayed
mode
Off: bASE, basic parameters
displayed mode
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...