E5 Series High Performance Universal Inverter User’s Manual
Chapter 6 Parameter Descriptions
65
T: Auxiliary reference−50%: The auxiliary reference value subtracts the bias equal to 50% of the
auxiliary reference full range value. The main reference value is disable at this calculation formula.
3: Main ref auxiliary reference−50%: The auxiliary reference value subtracts the bias equal to
50% of the auxiliary reference full range value and then superimposes on the main reference.
Figure6−6 Auxiliary reference - 50% Figure6−7 Main ref auxiliary reference - 50%
4: Max: Get the maximum value of the main reference f
m
and the auxiliary reference f
a
.
5: Min: Get the minimum value of the main reference f
m
and the auxiliary reference f
a
.
Frequency
Time
F
a
F
m
F
com
=MAX(F
m
, F
a
)
Fcom
Figure6−8 Take maximum value Figure6−9 Take minimum value
Note:
When the corresponding frequency of the combination value f
com
exceeds the frequency upper or lower
limit, the output frequency will be restricted to the upper or lower limit.
In analog feedback close loop system, digital voltage setting, analog and pulse can be set as main
reference channel; analog and pulse can be set as auxiliary reference channel.
The parameter PT.0T is used to set the main reference channel of process close loop control:
0: P8.00 setting T: AIT T: AIT 3: AI3 4: DI
The parameter PT.03 is used to set the auxiliary reference channel of process close loop control:
0: None T: AIT T: AIT 3: AI3 4: DI
The parameter PT.04 is used to set the main reference and auxiliary reference calculation formula of
process close loop control:
0: Main + auxiliary
T: Main − auxiliary T: Auxiliary −50% 3: Main+ auxiliary−50%
4: Maximum 5: Minimum
The main reference and auxiliary reference calculation for close loop to the same as the main reference
and auxiliary reference calculation function for open loop. For details, refer to the description of PT.0T.
0 ~ 5(0)
Analog feedback close loop control main reference and auxiliary
reference calculation formula
PT.04
0 ~ 4(0)
Analog feedback close loop control auxiliary reference channel
PT.03
0 ~ 4(0)
Analog feedback close loop control main reference channel
PT.0T
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...