E5 Series High Performance Universal Inverter User’s Manual
Chapter 6 Parameter Descriptions
85
The analog values input via AIT, AIT and AI3 terminals usually have certain interference signals. It can
amplify the setup value of AI filter time properly to improve the anti−interference capability.
AIT, AIT and AI3 can be configured as multi-function digital input terminal, when the parameter value are
set to “99”, the analog configured as analog input, else configured as multi-function digital input.
When AIT, AIT and AI3 configured as multi-function digital input terminal, the terminal function is the
same as XT to X7. Refer to the parameter descriptions of P5.00 to P5.06.
Note:
If the analog input has been configured as multi-function digital input terminal, then the following limit
values apply:
≤
3V DC
—
>“OFF”, means the terminal function is disabled.
≥
7V DC
—
>“ON”, means the terminal function is enabled.
0.000 ~T.000 s (0.004s)
AIT filter time
P6.T3
P6.T6
AIT configured as multi-function digital input terminal
00 ~ 99 (99)
00 ~ 99 (99)
P6.T7
00 ~ 99 (99)
AIT configured as multi-function digital input terminal
AI3 configured as multi-function digital input terminal
P6.T5
0.000 ~T.000 s (0.004s)
AI3 filter time
P6.T4
0.000 ~T.000 s (0.004s)
AIT filter time
P6.TT