Chapter 8 Maintenance and Inspection
The application environment (such as temperature, humidity, dust and powder, wool, smoke and
oscillation), burning and wearing of internal devices and other factors may reduces the service life. To
reduce the fault and prolong the service life, it is necessary to perform daily inspections and periodic
maintenance.
Note
Note
T. Only the professionals can dismantle and replace the components.
T. Before inspection and maintenance, please make sure that the power supply to the has been shut
down for at least ten minutes or the CHARGER indicator is OFF, otherwise, electric shock may be
happened (E5−H−4TTTG and above power class, E5−A−4TT5 and above power class has CHARGER
indicator).
3. Do not leave metal components and parts in the inner of inverter, otherwise, inverter me be damaged.
8.T Daily Inspections
The inverter should be used under the allowable conditions as recommended in this manual and its daily
inspections should be performed as the table.
Item
Inspection Contents
Inspection Means
Criteria
Environment
Temperature
Thermometer
−T0 ~ +40ºC
De-rated at 40 to 50ºC, and the rated
output current shall be decreased by
T% for every temperature rise of TºC.
Humidity
hygrometer
5 ~ 95%, no condensing
Dust, oil, water and drop Visual check
No dust, no oil, no water and no drop
Vibration
Special test instrument
3.5mTs
T
, T~ 9Hz
T0mTs
T
,9~ T00Hz
T5mTs
T
,T00~ 500Hz
Gas
Special test instrument,
smell check and visual
check
No abnormal smell and no smoke
Inverter
Heat dissipation effect
Special test instrument
Exhaust normal
Noise
Listen
There is no abnormal noise
Gas
Smell and visual check
There are no abnormal smell and
smoke
Physical appearance
Visual check
The physical appearance is kept
intact
Heat-sink fan ventilation Visual check
There are no fouling and wool that
block the air duct
Input current
Ampere-meter
In the allowable operating range, refer
to the nameplate
Input voltage
Voltmeter
In the allowable operating range, refer
to the nameplate
Output current
Ampere-meter
In the rated value range. It can be
overloaded for a short while
Output voltage
Voltmeter
In the rated value range
Motor
Heat dissipation effect
Special test instrument
and smell
There are no over temperature and
burning smell
Noise
Listen
There is no abnormal noise
Vibration
Special test instrument
There is no abnormal oscillation
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...