E5 Series High Performance Universal Inverter User’s Manual
50
Chapter 5 Parameter List
No.
Name
Default
Range
Unit Property
Description
User
Group P8 PID Close Loop Control parameters
P8.00
Analog feedback
process close loop
control digital voltage
reference
0.00
0.00 ~ T0.00
V
○
Digital voltage reference for process close loop
(if P0.03=TT3, PT.0T=0)
P8.0T
Single phase pulse
feedback process
close loop control
digital RPM reference
0
0 ~ 30000
rpm
○
0 ~ 30000
P8.0T
Pulse per turn for single
phase pulse
T000
T ~ 9999
T
×
T ~ 9999
P8.03 Proportional gain KP
0.T00
0 ~ T0.000
T
○
0.000 ~ T0.000
P8.04 Integral gain Ki
0.500
0 ~ T0.000
T
○
0.000 ~ T0.000
P8.05 Derivative gain Kd
0.000
0 ~ T0.000
T
○
0.000 ~ T0.000
P8.06 Sampling cycle
0.00T
0.00T ~ 30.000
s
○
0.00T ~ 30.000s
P8.07 PID deviation limit
5.0
0.0 ~ T0.0
%
○
0.0 ~ T0.0%
P8.08 PID integral property
00
00 ~ TT
T
○
Ones place: Whether to stop integral regulation
when the running frequency reaches the upper or
lower limit
0: Stop integral regulation
T: Continue integral regulation
Tens place: Output frequency direction:
0: Must be consistent with preset direction
T: Can regulation to reverse to preset direction
P8.09
PID positive or negative
function
0
0 ~ T
T
○
0: Positive
T: Negative
P8.T0
PID acceleration T
deceleration time
T0.0
0.0 ~ 6553.5
T
○
0 ~ 6553.5
Group P9 Motor Parameters
P9.00 Reserved
0
0 ~ T
T
×
Reserved
P9.0T Motor poles
4
T ~ TT8
T
×
T ~ TT8
P9.0T Motor rated speed
T500
0 ~ 30000
rpm
×
0 ~ 30000rpm
P9.03 Motor rated power
Factory
0.4 ~ 6553.5
kW
×
0.4 ~ 999.9kW
P9.04 Motor rated current
Factory
0.T ~ 6553.5
A
×
0.T ~ 999.9A
P9.05 No-load current I0
Factory
0.T ~ 6553.5
A
×
0.T ~ 999.9A
P9.06 Stator resistance RT
Factory
0 ~ 65.000
Ω
×
0.000 ~ 65.000Ω
P9.07
Stator leakage
inductance LT
Factory
0 ~ T000.0
mH
×
0.0 ~ T000.0mH
P9.08 Rotor resistance RT
Factory
0 ~ 65.000
Ω
×
0.000 ~ 65.000Ω
P9.09 Mutual inductance LT
Factory
0.0 ~ T000.0
mH
×
0.0 ~ T000.0mH
P9.T0
Magnetic flux saturation
coefficient T
87.00
0 ~ T00.00
%
×
0.0 ~ T00.00%
P9.TT
Magnetic flux saturation
coefficient T
80.00
0 ~ T00.00
%
×
0.0 ~ T00.00%
P9.TT
Magnetic flux saturation
coefficient 3
75.00
0 ~ T00.00
%
×
0.0 ~ T00.00%
P9.T3
Magnetic flux saturation
coefficient 4
7T.00
0 ~ T00.00
%
×
0.0 ~ T00.00%
P9.T4
Magnetic flux saturation
coefficient 5
70.00
0 ~ T00.00
%
×
0.0 ~ T00.00%
P9.T5 Motor data identification
0
0 ~ T
T
×
0: No action
T: Motor data identification at standstill
T: Complete motor data identification
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...