E5 Series High Performance Universal Inverter User’s Manual
Chapter 6 Parameter Descriptions
107
Pb.T0 Terminal UPTDN digital regulating frequency control
Ones place
Save after power off
0: Saved after power-off
T: Cleared after power-off
Tens place
Save after stop
0: Saved in stop status
T: Cleared after receive a stop command
T: Cleared in stop status
Hundreds place
Terminal UPTDN enabled setting
0: Only active when main reference is P0.05
T: Always active
T: Always inactive
Thousands place
Integral function selection
0: With integral function
T: Without integral function
Pb.T0 and Pb.TT are the same as the usage of operational panel
∧/∨
. For functions of terminal UPTDN,
refer to instructions of P5.00~P5.06.
Pb.T3 Reach pre-set running time action selection
Ones place
Continuous running time reached
0: Continue running
T: Stop and alarm
Tens place
Accumulative running time reached
0: Continue running
T: Stop and alarm
This parameter is use for inverter automatic stop and alarm or continue running once running time
reaches the user preset time. The parameters of Pb.T3, Pb.T4 defaults to 0, not timing.
From respond the run command, continuous running time reaches continuous running time setting (Pb.T3),
can output this signal through YTTYT terminal or relay terminal , and the YTTYT terminal function number
(P7.00TP7.0T) or relay terminal function number (P7.0T) is set to “T8: continuous running time reached”.
From the power on, running time reaches accumulative running time setting (Pb.T4), can output this
signal through YTTYT terminal or relay terminal, and the YTTYT function number (P7.00TP7.0T) or relay
terminal function number (P7.0T) set to “T7: accumulative running time reached”.
Note:
Accumulative running time and continuous running time will be reset to 0 if power off.
Continuous running time will be reset to 0 in stop status even power on.
Accumulative running time will not be reset to 0 in stop status. If accumulative running time output
signal is enabled, will become disabled in stop status and be reset to 0.
Continuous running time setting
Pb.TT
Reach pre-set running time action selection
00 ~ TT(00)
Pb.T3
0.0 ~ 6553.5 min (0.0 min)
Pb.T4
Accumulative running time setting
0.0 ~ 6553.5 min (0.0 min)
0.T ~ 50.0 s(T.0s)
Terminal UPTDN integral rate
Pb.TT
0000 ~ TTTT(000T)
Terminal UPTDN digital regulating frequency control
Pb.T0
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...