E5 Series High Performance Universal Inverter User’s Manual
Chapter 6 Parameter Descriptions
75
The following table lists the multi−function digital input terminal functions:
Setting
value
Function
Setting
value
Function
00
Jog forward
T7
Stop via terminal with DC braking T
0T
Jog reverse
T8
Counter input
0T
Forward (FWD)
T9
Counter reset
03
Reverse (REV)
30~3T
Reserved
04
Three−wire control
3T
Force to wake-up
05
Pulse frequency DI input ( X7TDI)
33~46
Reserved
06
Multi−step digital voltage terminal T
47
Single phase pulse input for closed loop control
07
Multi−step digital voltage terminal T
48
Run command is changed to operation panel
08
Multi−step digital voltage terminal 3
49
Run command is changed to terminal
09
Multi−step frequency terminal T
50
Run command is changed to communication
T0
Multi−step frequency terminal T
5T
Changeover between process close loop control
and open loop control
TT
Multi−step frequency terminal 3
5T
Main frequency reference is changed to digital
TT
Multi−step frequency terminal 4
53
Reserved
T3
AccelerationTdeceleration time terminal T
54
Main frequency reference is changed to AIT
T4
AccelerationTdeceleration time terminal T
55
Main frequency reference is changed to AIT
T5
Clear UPTDN regulation value
56
Main frequency reference is changed to AI3
T6
Terminal UP (frequency increase)
57
Main frequency reference is changed to DI
T7
Terminal DN (frequency decrease)
58
Auxiliary frequency reference is changed to NONE
T8
Acceleration and deceleration is prohibited
59
Reserved
T9
External fault input
60
Auxiliary frequency reference is changed to AIT
T0
Fault reset (RESET)
6T
Auxiliary frequency reference is changed to AIT
TT
Run pause
6T
Auxiliary frequency reference is changed to AI3
TT
Run is prohibited
63
Auxiliary frequency reference is changed to DI
T3
Stop via terminal
64~66
Reserved
T4
Coast to stop via terminal
67
Process closed loop output forced to 0
T5
Stop via terminal with DC braking T
68
PID positive logic or negative logic selection
T6
Emergency stop T (fastest stop)
69~98
Reserved
00: Terminal jog forward input
0T: Terminal jog reverse input
0T: Terminal run forward input (FWD)
03: Terminal run reverse input (REV)
The functions of above items 0 to 3 are only enabled when the run command reference channel is
terminal (P0.06=T). Terminal run command and jog run command should be interlocked.
04: Three−wire control
It is only enabled in the terminal run command reference mode (P0.06=T). Refer to parameter P5.TT.
05: Pulse frequency DI input (only available for X7TDI terminal)
When the pulse frequency DI input acts as the reference (e.g. P0.04=4 or PT.0T=4), this function
must be selected for the X7TDI terminal.
Summary of Contents for E5 Series
Page 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Page 7: ...vi T Setting Process for Open Loop ...
Page 8: ...vii Open loop setting process continued ...
Page 9: ...viii 3 Setting Process for Closed Loop ...
Page 10: ...ix Setting Process for Closed Loop continued ...