E6581381
A-19
1
(2)
CT and ammeter
If a CT and ammeter are connected externally to detect inverter output current, the leak current's high
frequency component may destroy the ammeter. If the wires are more than 50 meters long, it will be
easy for the high frequency component to pass through the externally connected CT and be
superimposed on and burn the ammeter with models having motors of low rated current (several
A(ampere) or less), especially the 400V class low capacity (5.5kW or less) models, because the leak
current will increase in proportion to the motor's rated current.
Remedies:
1.Use a meter output terminal in the inverter control circuit.
The load current can be output on the meter output terminal (FM). If the meter is connected, use an
ammeter of 1mAdc full scale or a voltmeter of 7.5V-1mA full scale.
0-20mAdc (4-20mAdc) can be also output.
⇒
See section 5.4.
2.Use the monitor functions built into the inverter.
Use the monitor functions on the panel built into the inverter to check current values.
⇒
See section 8.1.1.
1.4.4 Installation
■
Installation environment
The VF-FS1 Inverter is an electronic control instrument. Take full consideration to installing it in the proper
operating environment.
Danger
Prohibited
•
Do not place any inflammable substances near the VF-FS1 Inverter.
If an accident occurs in which flame is emitted, this could lead to fire.
Mandatory
•
Operate under the environmental conditions prescribed in the instruction manual.
Operations under any other conditions may result in malfunction.
Warning
Prohibited
•
Do not install the VF-FS1 Inverter in any location subject to large amounts of vibration.
This could cause the unit to fall, resulting in bodily injury.
Mandatory
•
Check to make sure that the input power voltage is +10%, -15% of the rated power voltage written on
the rating label (
±
10% when the load is 100% in continuous operation) If the input power voltage is not
+10%, -15% of the rated power voltage (
±
10% when the load is 100% in continuous operation) this
may result in fire.
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......