[Selection 2: Setting vector control and manual tuning independently]
If an "
GVP
" tuning error is displayed during auto-tuning or when vector control characteristics are to be
improved, independent motor constants can be set.
Title
Function
Adjustment range
Default setting
H
Slip frequency gain
0-150 (%
)
50
H
Automatic torque boost value
0.0-30.0 (%)
H
Motor rated current
0.1-200.0 (A)
H
Motor no-load current
10-100 (%)
H
Motor rated rotational speed
100-15000 (min
-1
)
Depends on the
capacity
(
⇒
See page K-14)
H
Speed control response
coefficient
1-150
40
H
Speed control stability
coefficient
1-100
20
Setting procedure Adjust the following parameters:
H
: Set the compensation gain for the slipping of the motor. A higher slip frequency reduces motor
slipping correspondingly. After setting
H
, set
H
to adjust in detail.
H
: Adjust the primary resistive component of the motor. Use the auto-tuning value.
H
: Set the rated current of the motor. For the rated current, see the motor's nameplate or test report.
H
: Set the ratio of the no-load current of the motor to the rated current. Enter the value in % that is
obtained by dividing the no-load current specified in the motor's test report by the rated current.
H
: Set the rated rotational speed of the motor. For the rated current, see the motor's nameplate or test
report.
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......