6.21.2 Using the RS485
■
Setting the communication functions
Setting commands and frequencies by communications has priority over sending commands from the
operation panel or the terminal board. Command/frequency setting by communications can therefore be
enabled, irrespective of the setting in the command mode (
EOQF
) or the frequency setting mode (
HOQF
).
When inverters are connected to each others, however, in order for slave inverters to recognize frequency
signals from the master inverter as frequency commands, the frequency setting mode selection 1 parameter
(
HOQF
) provided for each slave inverter needs to be set to 4 (serial communications). Refer to the
COMMUNICATIONS EQUIPMENT USER'S MANUAL for details.
However, when the input terminal function selection parameter is set to 48: SC/LC (Serial/Local selection),
the inverter can be operated with the settings of the command mode (
EOQF
) or the frequency setting mode
(
HOQF
) by external input.
■
Transmission specifications
Item
Specifications
Transmission scheme
2-wire, Half-duplex
Connection scheme
Centralized control
Synchronization scheme
Asynchronous
Transmission rate
Default: 19200 baud (parameter setting)
Option: Either 9600 or 19200 baud
Character transmission
ASCII code: JIS X 0201 8, 8-bit (fixed)
Binary code: Binary, 8-bit (fixed)
Stop bit length
Inverter receiving: 1 bit, Inverter sending: 2 bits
Error detection
Parity: Even, Odd, or None selectable by parameter setting;
check sum method
Character transmission format
Receiving: 11-bit, Sending: 12-bit
Order of bit transmission
Least significant bit first
Frame length
Variable to a maximum of 17 bytes
■
Example of connection for RS485-communication
<Example of connection>
Host computer
VF-FS1
VF-FS1
VF-FS1
VF-FS1
Option
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......