E6581381
F-4
6
If the detection band value + the set frequency is less than the designated frequency
Set frquency speed reach signal
RY-RC terminals
FLA-FLC-FLB terminals
Set frequency speed reach signal:
Inverted
Output frequency [Hz]
Time [s]
H
-
H
ON
OFF
H
+
H
H
ON
OFF
0
6.2
Input signal selection
6.2.1 Changing the functions of VIA terminal
H
: VIA terminal function selection
•
Function
This parameter allows you to choose between signal input and contact signal input for the VIA terminal.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Analog/contact input
function selection
(VIA terminal)
0: VIA - analog input
1: VIA
-
contact input (Sink)
2: VIA
-
contact input (Source)
0
*
When using the VIA terminal as contact input terminals in sink logic connection, be sure to insert a
resistor between the P24 terminal and the VIA terminal. (Recommended resistance: 4.7k
Ω
-1/2W)
Note: When using the VIA terminal as a contact input terminal, be sure to turn the VIA (SW3) slide switch to
the V position.
+
The figure on the right shows an example of the
connection of input terminal VIA when it is used as
contact input terminal. This example illustrates the
connection when the inverter is used in sink
(Negative) logic mode.
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......