E6581381
K-9
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0496
Waveform switching
adjustment
coefficient
kHz
0.1/0. 1
0.1-14.0
14.0
5.10
6.15.2
*1 : Default values vary depending on the capacity.
⇒
See the table of page K-14.
•
Acceleration/deceleration time parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0500
Acceleration time
2
s
0.1/0.1
0.0-3200
* 1
H
0501
Deceleration time
2
s
0.1/0.1
0.0-3200
* 1
H
0502
Acceleration/decel
eration 1 pattern
-
-
0
H
0503
Acceleration/decel
eration 2 pattern
-
-
0: Linear
1: S-pattern 1
2: S-pattern 2
0
H
0504
Selecting an
acceleration/decel
eration pattern
-
-
1: Acceleration/deceleration 1
2: Acceleration/deceleration 2
1
H
0505
Acceleration/decel
eration 1 and 2
switching
frequency
Hz
0.1/0.01
0.0-
WN
0.0
H
0506
S-pattern lower-
limit adjustment
amount
%
1/1
0-50
10
6.16
H
0507
S-pattern upper-
limit adjustment
amount
%
1/1
0-50
10
*1 : Default values vary depending on the capacity.
⇒
See the table of page K-14.
•
Protection parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0601
Stall prevention
level 1
%
(A)
1/1
10-110
,
111 (disabled)
110
6.17.2
H
0602
Inverter trip
retention selection
-
-
0: Canceled with the power off
1: Still retained with the power off
0
6.17.3
H
0603
Emergency stop
selection
-
-
0: Coast stop
1: Slowdown stop
2: Emergency DC braking
0
6.17.4
H
0604
Emergency DC
braking time
s
0.1/0.1
0.0-20.0
1.0
H
0605
Output phase
failure detection
mode selection
-
-
0: Disabled
1: At start-up (only one time after
power is turned on)
2: At start-up (each time)
3: During operation
4: At start-up + during operation
5: Detection of cutoff on output side
0
6.17.5
H
0607
Motor 150%-
overload time limit
s
1/1
10-2400
300
6.17.1
H
0608
Input phase failure
detection mode
selection
-
-
0: Disabled, 1: Enabled
1
6.17.6
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......