6
6.20.6 Selection of operation panel stop pattern
H
: Selection of operation panel stop pattern
•
Function
This parameter are used to select a mode in which the motor started by pressing the key on the
operation panel is stopped when the key is pressed.
1)
Slowdown stop
The motor slows down to a stop in the deceleration time set with
FGE
(or
H
).
2)
Coast stop
The inverter cuts off power supply to the motor. The motor comes to a stop after coasting for a while by
inertia. Depending on the load, the motor may keep running for a good long time.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Selection of operation panel stop
pattern
0: Slowdown stop
1: Coast stop
0
6.20.7 Display of the head of the parameters
H
: Head of the parameter display selection
•
Function
The parameter can be set at the front of the setting monitor mode.
If selecting “1:
CWJ
”, the Wizard parameter “
CWH
” is not displayed.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Head of parameter display
selection
0: AUF
1: AUH
0
6.20.8 Integral output power
H
: Integral output power retention selection
H
: Integral output power display unit selection
•
Function
At the main power off ,it is selectable whether retention of integral output power values or not.
And also, the display unit is selectable.
STOP
RUN
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......