6.10 Bumpless operation
H
: Bumpless operation selection
•
Function
When switching from Remote mode to Local mode using key, the status of start and stop, and
operating frequency at Remote mode are moved to Local mode.
By contraries, when switching from Local mode to Remote mode, they are not moved to Remote
mode.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Bumpless operation selection
0: Disabled
1: Enabled
1
Example : Remote mode (
EOQF
(Terminal board))
Remote mode
Local mode
ON
OFF
ON
OFF
ON
OFF
Key
Output
frequency
F-CC
Internal
operation
command
Local mode
Remote mode
ON
OFF
ON
OFF
ON
OFF
Key
Output
frequency
F-CC
Internal
operation
command
Set frequency at
Remote mode
Setting frequency and start/stop
status are moved to Local mode
when switching from Remote
mode to Local mode.
Motor runs continuously like an
example.
When switching from Local
mode to Remote mode, setting
frequency and start/stop status
are determined by Remote
mode status.
The example shows the motor
runs continuously because the
Remote mode is “run” status.
To prevent from moving the setting frequency and start/stop status of Remote mode to Local mode,
the
H
is set to “
”(Disabled). In this case, key is effective only while stopping.
LOC
REM
LOC
REM
LOC
REM
LOC
REM
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......