[Prealarm display]
E
Overcurrent alarm
Same as
QE
(overcurrent)
R
Overvoltage alarm
Same as
QR
(overvoltage)
N
Overload alarm
Same as
QN
and
QN
(overload)
J
Overheat alarm
Same as
QJ
(overheat)
If two or more problems arise simultaneously, one of the following alarms appears and blinks.
ER
,
RN
,
ERN
The blinking alarms
E
,
R
,
N
,
J
are displayed in this order from left to right.
13.2 Restoring the inverter from a trip
Do not reset the inverter when tripped because of a failure or error before eliminating the cause. Resetting the
tripped inverter before eliminating the problem causes it to trip again.
The inverter can be restored from a trip by any of the following operations:
(1) By turning off the power (Keep the inverter off until the LED turns off.)
Note:
⇒
See section 6.17.3 (inverter trip retention selection
H
) for details.
(2) By means of an external signal (Short circuit between RES and CC on terminal board
→
Open)
(3) By operation panel operation
(4) By inputting a trip clear signal from a remote input device
(Refer to the remote input device operating manual for details.)
To reset the inverter by operation panel operation, follow these steps.
1.
Press the key and make sure that
ENT
is displayed.
2.
Pressing the key again will reset the inverter if the cause of the trip has already been eliminated.
+
In case of a trip due to overheating (
QJ
), the inverter checks the temperature within. Wait until the
temperature in the inverter falls sufficiently before resetting the inverter.
[Caution]
Turning the inverter off then turning it on again resets the inverter immediately. You can use this mode of
resetting if there is a need to reset the inverter immediately. Note, however, that this operation may damage
the system or the motor if it is repeated frequently.
STOP
STOP
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......