E6581381
F-41
6
6.14 Conducting PID control
H
: PID control waiting time
H
: PID control
H
: Proportional gain
H
: Integral gain
H
: Differential gain
•
Function
Using feedback signals (4 to 20mA, 0 to 10V) from a detector, process control can be exercised, for
example, to keep the airflow, amount of flow or pressure constant.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
PID control waiting time
0-2400 [s]
0
H
PID control
0: Disabled
1: Enabled (Feedback: VIA)
2: Enabled (Feedback: VIB)
0
H
Proportional gain
0.01-100.0
0.30
H
Integral gain
0.01-100.0
0.20
H
Differential gain
0.00-2.55
0.00
1) External connection