![Toshiba TOSVERT VF-FS1 Series Instruction Manual Download Page 204](http://html.mh-extra.com/html/toshiba/tosvert-vf-fs1-series/tosvert-vf-fs1-series_instruction-manual_425671204.webp)
E6581381
J-2
10
■
Selection of wiring devices
Input current (A)
Molded case circuit
breaker (MCCB)
Earth leakage circuit
breaker (ELCB)
Magnetic contactor
(MC)
Voltage class
Capacity of
applicable
motor
(kW)
200V class:200V
400V class:380V
200V class:240V
400V class:480V
Inverter model
Rated current (A)
Operational current(A)
AC-1
0.4
1.9
1.6
VFFS1-2004PM
3
25
0.75
3.3
2.7
VFFS1-2007PM
5
25
1.5
6.1
5.1
VFFS1-2015PM
10
25
2.2
8.7
7.3
VFFS1-2022PM
15
25
4
15.7
13.0
VFFS1-2037PM
30
25
5.5
20.8
17.3
VFFS1-2055PM
40
32
7.5
27.9
23.3
VFFS1-2075PM
50
40
11
42.1
34.4
VFFS1-2110PM
75
50
15
56.1
45.5
VFFS1-2150PM
100
80
18.5
67.3
55.8
VFFS1-2185PM
100
80
22
80.4
66.4
VFFS1-2220PM
125
100
Three-phase
200V class
30
113.3
89.5
VFFS1-2300PM
175
125
0.4
1.0
0.8
VFFS1-4004PL
3
25
0.75
1.7
1.4
VFFS1-4007PL
3
25
1.5
3.2
2.5
VFFS1-4015PL
5
25
2.2
4.6
3.6
VFFS1-4022PL
10
25
4
8.1
6.4
VFFS1-4037PL
15
25
5.5
10.9
8.6
VFFS1-4055PL
20
25
7.5
14.7
11.7
VFFS1-4075PL
30
32
11
21.1
16.8
VFFS1-4110PL
40
32
15
28.5
22.8
VFFS1-4150PL
50
40
18.5
34.8
27.8
VFFS1-4185PL
60
50
22
41.6
33.1
VFFS1-4220PL
75
80
Three-phase
400V class
Note 4)
30
56.7
44.7
VFFS1-42300PL
100
80
Note 1: Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
Note 2: Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
Note 3: When using on the motor side during commercial-power supply operation, choose the MC with class
AC-3 rated current for the motor rated current.
Note 4: Attach surge killers to the magnetic contactor and exciting coil of the relay.
Note 5: In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit,
raise the reliability of the contact by using 2a-type contacts in parallel connection.
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......