Auto-stop in case of lower-limit frequency continuous
operation
6.8.1 Auto-stop in case of lower-limit frequency continuous
operation
H
: Auto-stop in case of lower-limit frequency continuous operation
•
Function
If operation is carried out continuously at a frequency command below the lower-limit frequency (
NN
) for
the period of time set with
H
, the inverter will automatically slow down the motor to a stop. At that
time, “
NUVR
” is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency (
NN
) +0.2Hz.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Auto-stop in case of lower-limit
frequency continuous operation time
0.0: Disabled
0.1-600.0 (s)
0.0
Note: This function is enabled even at the start of operation and during switching between forward and
reverse run.
Output frequency [Hz]
NN
+0.2Hz
NN
Operation signal (F or R)
Time [s]
H
ON
OFF
H
H
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......