E6581381
L-2
12
■
Common specification
Item
Specification
Control system
Sinusoidal PWM control
Rated output voltage
Adjustable within the range of 50 to 660V by correcting the supply voltage (not adjustable above the input
voltage)
Output frequency range
0.5 to 200.0Hz, default setting: 0.5 to 80Hz, maximum frequency: 30 to 200Hz
Minimum setting steps
of frequency
0.1Hz: analog input (when the max. frequency is 100Hz), 0.01Hz: Operation panel setting and
communication setting.
Frequency accuracy
Digital setting: within ±0.01% of the max. frequency (-10 to +60°C)
Analog setting: within ±0.5% of the max. frequency (25°C ±10°C)
Voltage/frequency
characteristics
V/F constant, variable torque, automatic torque boost, vector control, automatic energy-saving, PM motor
control. Auto-tuning. Base frequency (25 - 200Hz) adjusting to 1 or 2, torque boost (0 - 30%) adjusting to
1 or 2, adjusting frequency at start (0.5 - 10Hz)
Frequency setting
signal
External frequency potentiometer (connectable to a potentiometer with a rated impedance of 1 - 10k
Ω
), 0
- 10Vdc (input impedance: VIA/VIB=30k
Ω
, 4 - 20mAdc (Input impedance: 250
Ω
).
Terminal board base
frequency
The characteristic can be set arbitrarily by two-point setting. Possible to set individually for three
functions: analog input (VIA and VIB) and communication command.
Frequency jump
Three frequencies can be set. Setting of the jump frequency and the range.
Upper- and lower-limit
frequencies
Upper-limit frequency: 0 to max. frequency, lower-limit frequency: 0 to upper-limit frequency
PWM carrier frequency
Adjustable within a range of 6.0 to 16.0Hz (default: 8 or 12kHz).
Pr
incip
al contr
ol f
un
ct
ions
PID control
Setting of proportional gain, integral gain, differential gain and control wait time. Checking whether the
amount of processing amount and the amount of feedback agree.
Acceleration/decelerati
on time
Selectable from among acceleration/deceleration times 1 and 2 (0.0 to 3200 sec.). Automatic
acceleration/deceleration function. S-pattern acceleration/deceleration 1 and 2 and S-pattern adjustable.
Control of forced rapid deceleration and dynamic rapid deceleration
DC braking
Braking start-up frequency: 0 to maximum frequency, braking rate: 0 to 100%, braking time: 0 to 20
seconds, emergency DC braking
Input terminal function
(programmable)
Possible to select from among 57 functions, such as forward/reverse run signal input, operation base
signal input and reset signal input, to assign to 4 input terminals. Logic selectable between sink and
source.
Output terminal
functions
(programmable)
Possible to select from among 58 functions, such as upper/lower limit frequency signal output, low speed
detection signal output, specified speed reach signal output and failure signal output, to assign to FL
relay output, RY output terminals.
Forward/reverse run
The RUN and STOP keys on the operation panel are used to start and stop operation, respectively. The
switching between forward run and reverse run can be done from one of the three control units: operation
panel, terminal board and external control unit.
Preset speed operation
Base fre 7-speed operation possible by changing the combination of 3 contacts on the terminal
board.
Retry operation
Capable of restarting automatically after a check of the main circuit elements in case the protective
function is activated. 10 times (Max.) (selectable with a parameter)
Various prohibition
settings
Possible to write-protect parameters and to prohibit the change of panel frequency settings and the use
of operation panel for operation, emergency stop or resetting.
Auto-restart operation
In the event of a momentary power failure, the inverter reads the rotational speed of the coasting motor
and outputs a frequency appropriate to the rotational speed in order to restart the motor smoothly. This
function can also be used when switching to commercial power.
Drooping function
The motor is allowed to “slip” according to the load torque current.
O
per
at
ion speci
ficat
ions
Failure detection signal
1c-contact output: (250Vac-0.5A-cos
Ф
=0.4)
<Continued overleaf>
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......