Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Note1: The heat loss for the optional external devices (input reactor, radio noise reduction filters, etc.) is not
included in the calorific values in the table
Note2: Case of 100% Load Continuation operation.
Calorific Values (w)
Voltage class
Operating motor
capacity
(kW)
Carrier frequency
8kHz
Carrier frequency
12kHz
Amount of forcible air
cooling ventilation required
(m
3
/min)
Heat discharge surface
area required for sealed
storage cabinet(m
2
)
0.4
-
44
0.25
0.88
0.75
-
63
0.36
1.26
1.5
-
101
0.58
2.02
2.2
-
120
0.68
2.4
4.0
-
193
1.1
3.86
5.5
-
249
1.42
4.98
7.5
-
346
1.97
6.92
11
-
459
2.62
9.18
15
-
629
3.59
12.58
18.5
698
-
3.98
13.96
22
763
-
4.35
15.26
Three-Phase
200V class
30
1085
-
6.18
21.7
0.4
-
45
0.26
0.9
0.75
-
55
0.31
1.1
1.5
-
78
0.44
1.56
2.2
-
103
0.59
2.06
4.0
-
176
1.0
3.52
5.5
-
215
1.23
4.3
7.5
-
291
1.66
5.82
11
-
430
2.45
8.6
15
-
625
3.56
12.5
18.5
603
-
3.44
12.06
22
626
-
3.57
12.52
Three-Phase
400V class
30
847
-
4.83
16.94
■
Panel designing taking into consideration the effects of noise
The inverter generates high frequency noise. When designing the control panel setup, consideration must be
given to that noise. Examples of measures are given below.
•
Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the
same conduit, do not run them parallel, and do not bundle them.
•
Provide shielding and twisted wire for control circuit wiring.
•
Separate the input (power) and output (motor) wires of the main circuit. Do not place them in the same
conduit, do not run them parallel, and do not bundle them.
•
Ground the inverter ground terminals (
).
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......