Error code
Failure code
Problem
Possible causes
Remedies
QR
000A
Overvoltage during
acceleration
•
The imput voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyrister is connected
to the same power distribution line.
•
A restart signal is input to the rotating
motor after a momentary stop, etc.
•
There is possibility of output phase
failure.
•
Insert a suitable input reactor.
•
Use
H
(auto-restart) and
H
(coast stop).
•
Check the main circuit output line, motor,
etc. for phase failure.
QR
000B
Overvoltage during
deceleration
•
The deceleration time
FGE
is too short.
(Regenerative energy is too large.)
•
H
(overvoltage limit operation) is
off.
•
The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened and closed.
(3) A system using a thyrister is connected
to the same power distribution line.
•
There is possibility of output phase
failure.
•
Increase the deceleration time
FGE
.
•
Enable
H
(overvoltage limit
operation).
•
Insert a suitable input reactor.
•
Check the main circuit output line, motor,
etc. for phase failure.
QR
000C
Overvoltage during
constant-speed
operation
•
The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyrister is connected
to the same power distribution line.
•
The motor is in a regenerative state
because the load causes the motor to run
at a frequency higher than the inverter
output frequency.
•
There is possibility of output phase
failure.
•
Insert a suitable input reactor.
•
Check the main circuit output line, motor,
etc. for phase failure.
QN
000D
Inverter overload
•
The acceleration time ACC is too short.
•
The DC braking amout is too large.
•
The V/F setting is improper.
•
A restart signal is input to the rotating
motor after a momentary stop, etc.
•
The load is too large.
•
Increase the acceleration time
CEE
.
•
Reduce the DC braking amount
H
and the DC braking time
H
.
•
Check the V/F parameter setting.
•
Use
H
(auto-restart) and
H
(coast stop).
•
Use an inverter with a larger rating.
QN
000E
Motor overload
•
The V/F setting is improper.
•
The motor is locked up.
•
Low-speed operation is performed
continuously.
•
An excessive load is applied to the motor
during operation.
•
Check the V/F parameter setting.
•
Check the load (operated machine).
•
Adjust
QNO
to the overload that the
motor can withstand during operation in a
low speed range.
*
QV
0020
Over-torque trip
•
Over-torque reaches to a detection level
during operation.
•
Enable
H
(over-torque trip
selection).
•
Check system error.
QJ
0010
Overheat
•
The cooling fan does not rotate.
•
The ambient temperature is too high.
•
The vent is blocked up.
•
A heat generating device is installed close
to the inverter.
•
The thermistor in the unit is broken.
•
Restart the operation by resetting the
inverter after it has cooled down enough.
•
The fan requires replacement if it does
not rotate during operation.
•
Secure sufficient space around the inverter.
•
Do not place any heat generating device
near the inverter.
•
Make a service call.
* You can select a trip ON/OFF by parameters.
(Continued overleaf)
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......