E6581381
K-3
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
RV
0015
V/F control mode
selection
-
-
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Energy-saving
5: - (Do not select)
6: PM motor control
2
5.10
XD
0016
Torque boost 1
%
0.1/0.1
0.0-30.0
* 2
5.11
VJT
0600
Motor electronic-
thermal protection
level 1
%
(A)
1/1
10-100
100
5.12
6.17.1
Setting
Overload protection OL stall
0
{
×
1
{
{
2
×
×
3
Standard
motor
×
{
4
{
×
5
{
{
6
×
×
QNO
0017
Electronic-thermal
protection
characteristic
selection *3
-
-
7
VF motor
×
{
0
5.12
UT
0018
Preset-speed
operation
frequency 1
Hz
0.1/0.01
NN
-
WN
15.0
UT
0019
Preset-speed
operation
frequency 2
Hz
0.1/0.01
NN
-
WN
20.0
UT
0020
Preset-speed
operation
frequency 3
Hz
0.1/0.01
NN
-
WN
25.0
UT
0021
Preset-speed
operation
frequency 4
Hz
0.1/0.01
NN
-
WN
30.0
UT
0022
Preset-speed
operation
frequency 5
Hz
0.1/0.01
NN
-
WN
35.0
UT
0023
Preset-speed
operation
frequency 6
Hz
0.1/0.01
NN
-
WN
40.0
UT
0024
Preset-speed
operation
frequency 7
Hz
0.1/0.01
NN
-
WN
45.0
5.13
H
-
Extended
parameters
-
-
-
-
-
4.2.2
ITW
-
Automatic edit
function
-
-
-
-
-
4.2.3
*1 : 230 (WP/WN type), 400 (WP type), 460 (WN type)
*2 : Default values vary depending on the capacity.
⇒
See the table of page K-14.
*3 :
{
: valid,
×
: invalid
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......