6.4
Basic parameters 2
6.4.1 Switching motor characteristics via terminal input
H
: Base frequency 2
H
: Base frequency voltage 2
H
: Torque boost 2
H
: Motor electronic-thermal protection level 2
H
: Stall prevention level 2
•
Function
Use the above parameters to switch the operation of two motors with a single inverter and to select
motor V/F characteristics (two types) according to the particular needs or operation mode.
Note: The
RV
(V/F control mode selection) parameter is enabled only for motor1.
If motor 2 is selected, V/F control will be given constant torque characteristics.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Base frequency 2
25.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
H
Base frequency voltage 2
50-330 (V) : 200V class
50-660 (V) : 400V class
230 (WP/WN type)
400 (WP type)
460(WN type)
H
Torque boost 2
0.0-30.0 (%)
Depending on model
(
⇒
See page K-14)
H
Motor electronic-thermal
protection level 2
10-100 (%) / (A)
100
H
Stall prevention level 2
10-110 (%) / (A),
111 : Disabled
110
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......