E6581381
F-23
6
6.7
DC braking
6.7.1 DC braking
H
: DC braking starting frequency
H
: DC braking current
H
: DC braking time
•
Function
A large braking torque can be obtained by applying a direct current to the motor. These parameters
set the direct current to be applied to the motor, the application time and the starting frequency.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
DC braking starting frequency
0.0-
HJ
(Hz)
0.0
H
DC braking current
0-100 (%) / (A)
50
H
DC braking time
0.0- 20.0 (sec)
1.0
Time [s]
DC braking starting frequency
H
DC braking current
H
DC braking time
H
Output frequency [Hz]
DC braking
Operation signal (F or R)
ON
OFF
Output current [A]
0
0
Set frequency
Note1: During DC braking, the overload protection sensitivity of the inverter increases. The DC braking
current may be adjusted automatically to prevent tripping.
Note 2: During DC braking, the carrier frequency is 6kHz irrespective of the setting of parameter
H
(PWM carrier frequency).
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......