Table of output terminal functions 1
Function
No.
Code
Function
Action
0
LL
Frequency lower limit
ON: The output frequency is above the
NN
set
value.
OFF: The output frequency is equal to or less than
the
NN
set value.
1
LLN
Inversion of frequency lower limit
Inversion of LL setting
2
UL
Frequency upper limit
ON: Output frequency is equal to or higher than
WN
value.
OFF: Output frequency is lower than
WN
value.
3
ULN
Inversion of frequency upper limit
Inversion of UL setting
4
LOW
Low-speed detection signal
ON: Output frequency is equal to or higher than
H
value.
OFF: Output frequency is lower than
H
value.
5
LOWN
Inversion of low-speed detection signal
Inversion of LOW setting
6
RCH
Designated frequency attainment signal
(completion of acceleration/deceleration)
ON: The output frequency is equal to or less than
the specified frequency ± frequency set with
H
.
OFF: The output frequency is above the specified
frequency ± frequency set with
H
.
7
RCHN
Inversion of designated frequency attainment
signal (inversion of completion of
acceleration/deceleration)
Inversion of RCH setting
8
RCHF
Set frequency attainment signal
ON: The output frequency is equal to or less than
the frequency set with
H
±
H
.
OFF: The output frequency is above the frequency
set with
H
±
H
.
9
RCHFN
Inversion of set frequency attainment signal
Inversion of RCHF setting
10
FL
Failure signal (trip output)
ON: When inverter is tripped
OFF: When inverter is not tripped
11
FLN
Inversion of failure signal (inversion of trip output)
Inversion of FL setting
12
OT
Over-torque detection
ON: Torque current is equal to or larger than
H
set value and longer than
H
set time.
OFF: The torque current is equal to or less than
(
H
set value -
H
set value).
13
OTN
Inversion of over-torque detection
Inversion of OT
14
RUN
Start/Stop
ON: When operation frequency is output or during
(
FD
)
OFF: Operation stopped
15
RUNN
Inversion of RUN/STOP
Inversion of RUN setting
16
POL
OL pre-alarm
ON: 50% or more of calculated value of overload
protection level
OFF: Less than 50% of calculated value of
overload protection level
17
POLN
Inversion of OL pre-alarm
Inversion of POL setting
20
POT
Over-torque detection pre-alarm
ON: Torque current is equal to or larger than 70%
of
H
set value.
OFF: The torque current is below (
H
set
value x 70% -
H
set value).
21
POTN
Inversion of over-torque detection pre-alarm
Inversion of POT setting
22
PAL
Pre-alarm
One of the following is turned on:
ON POL, POT, MOFF, UC, OT, LL stop, COT,
and instantaneous power failure coast stop.
or
E
,
R
,
J
issues an alarm
All the following are turned off:
OFF POL, POT, MOFF, UC, OT, LL stop,
COT, and instantaneous power failure coast
stop.
or
E
,
R
,
J
issues no alarm
Summary of Contents for TOSVERT VF-FS1 Series
Page 2: ......
Page 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Page 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Page 36: ......
Page 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Page 54: ......
Page 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Page 66: ......
Page 180: ......
Page 196: ......
Page 208: ......
Page 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Page 242: ......
Page 248: ......
Page 251: ......