![Thytronic XMR-A 4l+1A Manual Download Page 44](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984044.webp)
44
TECHNICAL DATA
I
ED
>>>>>
def
within CLP (
I
EDCLP
>>>>>
def
)
0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
Operating time (
t
ED
>>>>>
def
)
0.05...10.00 s (step 0.01 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup accuracy with measured residual voltage (
U
E
)
±
0.2%
Pickup accuracy with calculated residual voltage (
U
EC
)
±
1% with 0.01
U
ECn
±
0.5% with 0.1
U
ECn
Pickup accuracy (residual current)
±
1% with 0.01
I
En
±
0.3% with 1
I
En
Pickup accuracy (phase)
±
2° with 0.002
I
En
- 0.004
U
En
±
0.2° with 0.005
I
En
- 0.01
U
En
±
0.2° with 0.1
I
En
- 0.5
U
En
±
0.3% with 1
I
En
Operate time accuracy
5% ± 10 ms
—
Out of step - 78
Setpoints
78 threshold delta AL
0 ....180
deg
(step 1
deg
)
78 threshold delta TR
0 ....180
deg
(step 1
deg
)
78 Reset time delay
0.05...30.00 s (step 0.01 s)
Alarm 1 Operating time
0 ...500 ms (step 1 ms)
Alarm 1 Hold time
0 ...1000 ms (step 1 ms)
TripA Hold time
0 ...1000 ms (step 1 ms)
TripB Hold time
0 ...1000 ms (step 1 ms)
78 threshold Zone A
1 ... 20 (step 1)
78 threshold Zone B
1 ... 20 (step 1)
Blocking parameters
78
I2
> threshold
0.05 ...5.00
I
B
(0.01
I
B
)
78
I1
< threshold
0.10 ...4.00
I
B
(0.01
I
B
)
78
U>
threshold
0.50 ...1.50
U
n
(0.01
U
n
)
—
Overfrequency - 81O
f> Element
Definite time
First threshold definite time (
f>
def
) 1.000....1.200
f
n
(step 0.001
f
n
)
Operating time (
t
f
>
def
)
0.05...100.00
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
f>> Element
Definite time
Second threshold definite time (
f>>
def
)
1.000....1.200
f
n
(step 0.001
f
n
)
Operating time (
t
f
>>
def
)
0.05...100.00
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout ratio
≥
0.998
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Reference values
rest: setting value - 0.2 Hz
trip: setting value + 0.2 Hz
Pickup accuracy
±5 mHz with 0.02
U
n
,
±
2 mHz with 1
U
n
Operate time accuracy
5%
±
10 ms
—
Underfrequency - 81U
f< Element
Definite time
First threshold definite time (
f<
def
) 0.800...1.000
f
n
(step 0.001
f
n
)
Operating time (
t
f
<
def
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
f<< Element
Definite time
Second threshold definite time (
f<<
def
)
0.800...1.000
f
n
(step 0.001
f
n
)
Operating time (
t
f
<<
def
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
f<<< Element