FUNCTION CHARACTERISTICS
219
—
Minimum power factor - 55
Preface
Two independent time adjustable thresholds with lag, lead or lag/lead programmable power factor.
For each elements can a consensus for start / trip operation may be set only if the circuit breaker is
closed and after an adjustable enabling time, the closure (tARM-cosphi<) .
Operation and settings
The power factor is computed:
± cos
f
=
± P
/
S
where:
• P
is the total active power:
± P
=
U
L1
·
I
L1
·
cos
f
L1
+
U
L2
·
I
L2
·
cos
f
L2
+
U
L3
·
I
L3
·
cos
f
L3
• S is the total apparent power:
S
= √
P
2
+
Q
2
The lag power factor (
cos
f
=
P
/S with
Q
≥ 0) and the lead power factor are compared with the setting
value (
cos
f
lag
<,
cos
f
lead
<).
-Q
ϕ
lag
π
/2
π
−π
/2
−π
cos
ϕ
ϕ
lead
CPhi1<def
CPhi1<def
NO TRIP
NO TRIP
TRIP
TRIP
+Q
+P
-P
TRIP
CPhi1<def
CPhi1<def
TRIP
TRIP
TRIP
NO TRIP
NO TRIP
Tripping direction setting: CosPhi Lag/Lead
General operation characteristic for the out of step element - 55
-Q
ϕ
lag
π
/2
π
−π
/2
−π
cos
ϕ
ϕ
lead
CPhi1<def
NO TRIP
TRIP
+Q
+P
-P
TRIP
CPhi1<def
TRIP
NO TRIP
NO TRIP
NO TRIP
Tripping direction setting: CosPhi Lag
General operation characteristic for the out of step element - 55
-Q
ϕ
lag
π
/2
π
−π
/2
−π
cos
ϕ
ϕ
lead
CPhi1<def
NO TRIP
TRIP
+Q
+P
-P
CPhi1<def
TRIP
TRIP
NO TRIP
NO TRIP
NO TRIP
Tripping direction setting: CosPhi Lead
General operation characteristic for the out of step element - 55
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021