TECHNICAL DATA
21
—
Rated values (all versions)
Voltage measure
U
E
or
V
2
U
E
or
V
2
V
1
-
V
2
Phase correction
0...360 ° (step 1°)
Synchro-check voltage measure
V
1
U
12
or
U
L1
Relay nominal frequency (
f
n
)
50, 60 Hz
Relay residual nominal current (
I
En
)
1 A or 5 A
3
Residual CT primary nominal current (
I
Enp
)
1 A...10 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...10000 A (step 100 A)
Relay phase to phase nominal voltage (
U
n
)
4
50...130 V (step 1 V)
200...520
V
(step 1 V)
Relay nominal voltage
V
2
-
U
n2
50...130 V (step 1 V)
Relay phase to ground nominal voltage (
E
n
)
E
n
=
U
n
/ √3
Relay calculated residual nominal voltage (
U
ECn
)
U
ECn
=
U
n
· √3 = 3 ·
E
n
Line VT primary nominal voltage (phase-to-phase) (
U
np
)
50 V...500 kV
50...499 V (step 1 V)
500...4990 V (step 10 V)
5000...49900 V (step 100 V)
50000...500000 V (step 1000 V)
Line VT primary nominal voltage - V2 side (
U
n2p
)
50 V...500 kV
50...499 V (step 1 V)
500...4990 V (step 10 V)
5000...49900 V (step 100 V)
50000...500000 V (step 1000 V)
Relay nominal active power (
P
n
)
P
n
= √3 ∙
U
n
∙
I
n
= 3 ∙
E
n
∙
I
n
Relay nominal reactive power (
Q
n
)
Q
n
= √3 ∙
U
n
∙
I
n
= 3 ∙
E
n
∙
I
n
Relay nominal apparent power (
S
n
)
S
n
= √3 ∙
U
n
∙
I
n
= 3 ∙
E
n
∙
I
n
—
Rated values for versions with inductive CT and VT inputs
Relay phase nominal current (
I
n
)
1 A or 5 A
Phase CT primary nominal current (
I
np
)
1 A...10 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...10000 A (step 100 A)
Relay measured residual nominal voltage (
U
En
)
50...130 V (step 1 V)
Residual primary nominal voltage (phase-to-phase) ∙√3 (
U
Enp
) 50 V...500 kV
50...499 V (step 1 V)
500...4990 V (step 10 V)
5000...49900 V (step 100 V)
50000...500000 V (step 1000 V)
—
Rated values for versions with ThySensor inputs
Phase sensor primary nominal current (
I
np
)
5
1 A...10 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...10000 A (step 100 A)
Relay phase to phase nominal voltage (
U
n
)
6
50...130 V (step 1 V)
—
Binary inputs
OFF/ON delay time (IN1
t
ON
, INx
t
ON
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
ON/OFF delay time (IN1
t
OFF
, INx
t
OFF
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Logic Active-ON/Active-OFF
—
Output relays
Minimum pulse width
0.000...0.500 s (step 0.005 s)
Logic De-energized/Energized
Operating
mode Latched/No
latched
—
Input sequence
Phase current sequence (
I-Sequence
)
IL1-IL2-IL3,
IL1-IL3-IL2....
Phase voltage sequence (
U-Sequence
)
UL1-UL2-UL3,
UL1-UL3-UL2,....
—
Polarity
A1-A2 Terminals polarity (A1-A2 POL)
NORMAL/REVERSE
Note 3 The nominal current settings doesn’t concern the protection elements; they must agree setting (1 A or 5 A)
Note 4 The setting ranges of the relay rated voltage U
R
are dependent on the purchased version (100 V or 400 V)
Nota 5 I
np
stays for the current value of rated primary current sensor (630 A) and is the reference to which all relay settings are expressed (I
n
)
Nota 6 U
n
is the reference to which all relay settings are expressed; a setting U
n
=100 V is equivalent to a 20 kV primary rated voltage of ThySensor
XMR-D EQUIPMENT MANUAL