FUNCTION CHARACTERISTICS
For all inverse time characteristics, following data applies:
• Asymptotic reference value (minimum pickup value): 1.1
I
E1
>
• Minimum operate time: 0.1
s
• Range where the equation is valid:
[1]
1.1 ≤
I
E1
/
I
E1
>
inv
≤ 20
• If
I
E1
>
inv
pickup ≥ 2.5
I
E1n
, the upper limit is 10
I
E1n
For all definite time elements the upper limit for measuring is 10
I
E1n
.
All residual overcurrent elements can be enabled or disabled by setting
ON
or
OFF
the
IE1>
Enable
,
IE1>> Enable
and/or
IE1>>> Enable
parameters inside the
Set \ Profile A (or B) \ Re-
sidual overcurrent-50N.1/51N.1 \
IE1> Element
(
IE1>> Element
,
IE1>>> Element) \ Setpoints
menus.
The first overcurrent element can be programmed with definite or inverse time characteristic by
setting the
IE1>Curve
parameter (
DEFINITE, IEC/BS A, IEC/BS B, IEC/BS C, ANSI/IEE
MI, ANSI/IEE VI, ANSI/IEE EI, EM
) available inside the
Set \ Profile A (or B) \ Residual overcur-
rent-50N.1/51N.1 \
IE1> Element \ Setpoints
menu.
The trip of IE1> element may be inhibited by the start of the second and/or third element (IE1>>,
IE1>>>) by setting
ON
the Disable IE1> by start IE1>>, Disable IE1> by start IE1>>> (
IE1>di-
sbyIE1>>, IE1>disbyIE1>>>
) parameters available inside the
Set \Profile A (or B) \ Residual
overcurrent-50N.1/51N.1 \ IE1>> Element
(
IE1>>> Element) \ Setpoints
menus.
Similarly the trip of the
I
E
>> element may be inhibited by start of the third element (
I
E
>>>) by setting
ON
the Disable IE>> by start IE>>> (
IE>>disbyIE>>>
) parameter available inside the
Set \ Profile
A (or B) \ Residual overcurrent-50N.1/51N.1 \ IE1>>> Element \ Setpoints
menu.
All the named parameters can be set separately for
Profile A
and
Profile B
An adjustable reset time delay is provided for every threshold
t
E1>RES
,
t
E1>>RES
,
t
E1>>>RES
).
Breaker failure (BF)
Each thresholds (IE1>, IE1>>, IE1>>>) can be associated to BF (H) and BF (L) protection by activating
the relative parameter in the matrices “Selection of function tripping for BF (H)” or “Selection of
function tripping for BF (L)” in relevant
BF
menus
[2]
:
• Set \ Profile A (or B) \ Breaker failure - BF side H
• Set \ Profile A (or B) \ Breaker failure - BF side L
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
Note 2 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
t-int-F50N-51N.ai
I
E1
I
E1
>>
I
E1
>>>
t
E1
>
t
E1
>>
t
E1
>>>
I
E1
>
t
General operation time characteristic for the residual overcurrent elements - 50N.1/51N.1
TRIP
Timers-F50N-51N.ai
IE1> Start
IE1> Trip
t
E1>
t
E1>
RESET
INPUT
t
E1>RES
t
E1>RES
t
E1>RES
t
IE> element residual overcurrent (50N.1/51N.1) - Timers
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021