TECHNICAL DATA
—
Relays
Quantity 7—11—15—31
Type
Changeover (SPDT, type C)
Make (SPST-NO, type A)
Rated current
8
A
Short duration current (0,5 s) 30
A
Rated voltage/max switching voltage
250 V~/400 V~
Make
1000
W/VA
Minimum switching load
300 mW (5 V/ 5 mA)
Life
• Mechanical
10
6
• Electrical
10
5
Breaking capacity:
• Direct current (L/R = 40 ms)
50 W
• Alternating current (
l
= 0,4)
1250 VA
Minimum pulse width
0....500 ms (step 5 ms)
—
Block output (Logic selectivity)
Quantity
1
Type
optocoupler
3.4
MMI (MAN MACHINE INTERFACE)
Display
60x85 graphic LCD
LEDs
Total Number
21
• ON/fail (Green)
1
• Remote
1
• Local
1
• Start (Yellow)
1
• Trip (Red)
1
• Programmables (Red)
16
Touchscreen Keyboard
10 keys
Keyboard
10
keys
3.5
COMMUNICATION INTERFACES
—
Local port
Ethernet 100 BaseT
100 Mbps
• Connector
RJ45
—
Network ports
RS485 1200...57600
bps
• Connection
screw terminals
Ethernet 100BaseT
[1]
100
Mbps
• Connection
Optical fiber 1300 nm, ST
100 Base TX, RJ45
—
Protocol
ModBus
RTU/IEC60870-5-103/DNP3,
ZCP/IP, IEC61850 Level A
Note [1] Two redundant port selectable with TX + TX or FX + FX connections. The secondary port
is activated in the event of failure of the primary port or by means of hw-sw switching command.
3.6
RATED VALUES AND GENERAL SETTINGS
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021