TECHNICAL DATA
31
10.0...40.0
I
n
(step 0.1
I
nH
)
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...9.99
I
n
(step 0.01
I
nH
)
10.0...40.0
I
n
(step 0.1
I
nH
)
Operating time (
t
(H)
>>
def
)
0.03...10.00 s (step 0.01 s)
Inverse time
Second threshold inverse time (
I
(H)
>>
inv
) 0.100...20.00
I
nH
0.100...0.999
I
n
(step 0.001 I
nH
)
1.00...20.00
I
n
(step 0.01 I
nH
)
Second threshold
within CLP (
I
(H)CLP>>inv
)
0.100...20.00
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...20.00
I
n
(step 0.01
I
nH
)
Operating time (
t
(H)
>>
inv
)
0.02...10.00 s (step 0.01 s)
I
(H)
>>> Element
CLP operating mode (
I
(H)CLP
>>>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
(H)CLP>>>
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
(H)
>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Third threshold definite time (
I
(H)
>>>
def
)
0.100...40.0
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...9.99
I
n
(step 0.01
I
nH
)
10.0...40.0
I
n
(step 0.1
I
nH
)
Third threshold
within CLP (
I
(H)CLP>>>def
)
0.100...40.0
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...9.99
I
n
(step 0.01
I
nH
)
10.0...40.0
I
n
(step 0.1
I
nH
)
Operating time (
t
(H)
>>>
def
)
0.03...10.00 s (step 0.01 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
0.5% with 0.1
I
nH
, ±
0.2% with 1
I
nH
Operate time accuracy
5% or ± 10 ms
Precisione tempi di intervento
5% ± 10 ms
—
Phase overcurrent - 50/51 side L
I
(L)
> Element
I
(L)
> Curve type (
I
(L)
>
Curve
) DEFINITE,
IEC/BS A, B, C, LIT, ANSI/IEEE MI, VI, EI
RECTIFIER,
I
2
t or EM
CLP operating mode (
I
(L)CLP>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
(L)CLP>
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
(L)
>
RES
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
First threshold definite time (
I
(L)
>
def
)
0.100...40.0
I
nL
0.100...0.999
I
n
(step 0.001
I
nL
)
1.00...9.99
I
n
(step 0.01
I
nL
)
10.0...40.0
I
n
(step 0.1
I
nL
)
First threshold within CLP (
I
(L)CLP>def
)
0.100...40.0
I
nL
0.100...0.999
I
n
(step 0.001
I
nL
)
1.00...9.99
I
n
(step 0.01
I
nL
)
10.0...40.0
I
n
(step 0.1
I
nL
)
Operating time (
t
(L)
>
def
)
0.04...200.00
s
0.04...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Inverse time
22
First threshold inverse time (
I
(L)
>
inv
)
0.100...20.00
I
nL
0.100...0.999
I
n
(step 0.001
I
nL
)
1.00...20.00
I
n
(step 0.01
I
nL
)
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021