FUNCTION CHARACTERISTICS
115
The element has two adjustable thresholds with time definite delay.
The active power is compared with the setting value (
P
1
<
def
,
P
2
<
def
) powers above the associated
pickup value are detected and a start is issued when the following conditions are met:
• The circuit breaker is closed (if the control is enabled)
• The
t
ARM-P
< adjustable timer has expired started from the CB closure
If all conditions are still met, after expiry of the associated operate time (
t
P1
<
def,
t
P2
<
def
) a trip com-
mand is issued; if instead the power exceed the threshold, the element is restored.
The elements can be enabled or disabled by setting
ON
or
OFF
the
State
parameter inside the
Set
\ Profile A (or B)\ Directional active underpower-37P \
P1< Element (P2< Element) \ Definite time
menu.
Enabling of the CB state control (
ON
or
OFF
of the
CB-37P
parameter) and adjustment of the waiting
time following the CB closing (
tARM-P<
parameter) maj be adjusted inside the
Set \ Profile A (or
B)\ Directional active underpower-37P \
P1< Element (P2< Element) \ Common configuration
menu.
The elements can be enabled or disabled by setting
ON
or
OFF
the
State
parameter inside the
Set
\ Profile A (or B)\ Directional active underpower-37P \
P1< Element (P2< Element) \ Definite time
menu.
Breaker failure (BF)
Each thresholds (P1<, P2>) can be associated to BF (H) and BF (L) protection by activating the rel-
ative parameter in the matrices “Selection of function tripping for BF (H)” or “Selection of function
tripping for BF (L)” in relevant
BF
menus
[1]
:
• Set \ Profile A (or B) \ Breaker failure - BF side H
• Set \ Profile A (or B) \ Breaker failure - BF side L
VT supervision (74VT)
The protection element is blocked off whenever the VT or/and CT supervision function are active,
so that no unwanted trip can arise if any fault on the VTs or/and CTs secondary circuits (break, fuse
trip, etc) are detect;
[2]
the Block functions enable from 74VT and 74CT parameter (
74VT-BK-EN
and
74CT-BK-EN
)
are available inside the
Set \ VT supervision -74VT
, and
Set \ CT supervision -74CT
menus
Logical block (Block1)
If the
P1<BLK1
and/or
P1<BLK1
enabling parameters is set to
ON
and a binary input is designed
for logical block (Block1), the protection is blocked whenever the given input is active.
The trip timer is held in reset condition, so the operate time counting starts when the input block
goes down.
[3]
The enabling parameters are available inside the
Set \ Profile A (or B)\ Directional
active underpower - 37P \
P1< Element P2< Element) \ Setpoints
menu, while the
Block1
function
must be assigned to the selected binary input inside the
Set \ Board1(2) inputs \ Binary input IN1-1...
INx-x
menus.
All parameters can be set separately for A and B setting profiles.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
Note 2 The exhaustive treatment of the VT and CT supervision function may be found inside the
CONTROL AND MONITORING
section.
Note 3 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside
CONTROL AND MONITOR-
ING
section.
P
P
1
<
t
t
P1
<
TRIP
P
1
<
TRIP
General operation time characteristic for the directional active power element - 37P (first element)
2nd Pickup Element
Block1
Block1
P
P
2
< Start
P
2
< Trip
1st Pickup Element
Common
Block1
Block1
P
P
1
< Start
P
1
< Trip
P
1<DIR
P
1<def
t
P1
<def
P
2<DIR
CB-37P
t
ARM-P<
P
2<def
t
P2
<def
General operation time characteristic for the directional active underpower elements - 37P
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021