TECHNICAL DATA
Overshoot time
0.04 s
Pickup
accuracy ±
0.5% with 0.1
U
n
/
E
n
±
0.2% with 1
U
n
/
E
n
Operate time accuracy
5% ±
10 ms
—
Positive sequence undervoltage - 27V1
U
1
< Element
Definite time
First threshold definite time (
U
1
<
def
)
0.05...1.10
E
n
(step 0.01
E
n
)
Operating time (
t
U1
<
def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout
ratio
1.03...1.05
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
5% with 0.01
U
n
, ±
0.3% with 0.15
U
n
Operate time accuracy
5% ±
10 ms
—
100% stator earth fault with 3rd harmonic (27H - 59H)
Configuration (
U
E3hmode
)
Minimum or Maximum
U
E3H
<threshold (
U
E3H
<
def
) 0.003...0.400
U
En
(step 0.001
U
En
)
Operating time (
t
E3H
<
def
)
0.07...100.0
s
0.07...0.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U
E3H
>threshold (
U
E3H
>
def
) 0.003...0.400
U
En
(step 0.001
U
En
)
Operating time (
t
E3H
>
def
)
0.07...100.0
s
0.07...0.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inhibit threshold
U
IN-3H
<
15
0.10...1.10
U
n
(step 0.01
U
n
)
Inhibit threshold
I
IN-3H
<
16
0.05...1.50
I
n
(step 0.01
I
n
)
Pickup time
≤
0.03 s (
U
E3H
< threshold)
≤
0.04 s (
U
E3H
> threshold)
Dropout ratio
1.03...1.08 (27H element)
0.95...0.98 (59H element)
Reset time
≤
0.05 s
Overshoot time
0.03 s
Reference values (27H element)
rest: 1.2
U
E3H
<, trip: 0.8
U
E3H
<
Reference values (59H element)
rest: 0.8
U
E3H
>, trip: 1.2
U
E3H
>
Pickup
accuracy ±
3% ±
0.5%
U
En
Operate
time
accuracy
5%
or
±
10 ms
—
Directional active overpower 32P
P1> Element
Setpoints
Tripping direction (
P
1
>
DIR
)
P Forward/P Reverse/P Forward-Reverse
Reset time delay (
t
P1
>
RES
)
0.00...100.0 s
Definite time
First threshold definite time (
P1>
def
)
0.01...1.50
P
n
Operating time (
t
P1
>
def
)
0.07...100.0
s
P2> Element
Setpoints
Tripping direction (
P
2
>
DIR
)
P Forward/P Reverse/P Forward-Reverse
Reset time delay (
t
P2
>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Second threshold definite time (
P2>
def
)
0.01...1.50
P
n
Operating time (
t
P2
>>
def
)
0.07...100.0 s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤ 0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤ 0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
3% with 0.01
P
n
, ±
0.5% with 0.1
P
n
Operate time accuracy
5% ± 10 ms
Note 15 The element is disabled when all the phase-to-phase voltages are below the
threshold set U
IN-3H
<
Note 16 The element is disabled when all the phase currents are below the
threshold set I
IN-3H
<