![Thytronic XMR-A 4l+1A Manual Download Page 36](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984036.webp)
36
TECHNICAL DATA
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...40.00
I
n
(step 0.01
I
n
)
Operating time (
t
E
>>
def
)
0.03...10.00 s (step 0.01 s)
Definite time for ThySensor versions:
Second threshold definite time (
I
EC
>>
def
0.010...30.0
I
n
0.010...0.999
I
n
(step 0.001
I
n
)
1.00...30.00
I
n
(step 0.01
I
n
)
I
EC
>>
def
within CLP (
I
ECCLP>>def
)
0.010...30.0
I
n
0.010...0.999
I
n
(step 0.001
I
n
)
1.00...30.00
I
n
(step 0.01
I
n
)
Operating time (
t
E
>>
def
)
0.03...10.00 s (step 0.01 s)
IEC>>> Element
CLP mode (
I
ECCLP
>>>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
ECCLP>>>
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
EC
>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time for CTs versions:
Third threshold definite time (
I
E
>>>
def
)
0.100...40.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...40.00
I
n
(step 0.01
I
n
)
I
EC
>>>
def
within CLP (
I
ECCLP>>>def
)
0.100...40.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...40.00
I
n
(step 0.01
I
n
)
Operating time (
t
EC
>>>
def
)
0.03...10.00 s (step 0.01 s)
Definite time for ThySensor versions:
Third threshold definite time (
I
E
>>>
def
)
0.010...30.0
I
n
0.010...0.999
I
n
(step 0.001
I
n
)
1.00...30.00
I
n
(step 0.01
I
n
)
I
EC
>>>
def
within CLP (
I
ECCLP>>>def
)
0.010...30.0
I
n
0.010...0.999
I
n
(step 0.001
I
n
)
1.00...30.00
I
n
(step 0.01
I
n
)
Operating time (
t
EC
>>>
def
)
0.03...10.00 s (step 0.01 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
4% with 0.1
I
ECn
, ±
1% with 1
I
ECn
Operate time accuracy
5% ± 10 ms
—
Minimum power factor - 55
Common configuration
CB-55 Delay (
t
ARM-CPhi
<)
0.07...300
s
0.07...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...300 s (step 0.1 s)
CPhi1< Element
Setpoints
Tripping direction (
CPhi1<
DIR
)
CosPhi Lag, CosPhi Lead,
CosPhi
Lag/Lead
Definite time
First threshold definite time (
CPhi1
<
def
)
0.10...0.99
(step
0.01)
Operating time (
t
CPhi1
<
def
)
0.04...100.0 s
0.04...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
CPhi2< Element
Tripping direction
(
CPhi2<
DIR
)
CosPhi Lag, CosPhi Lead,
CosPhi
Lag/Lead
Second threshold definite time (
CPhi2
<
def
)
0.10...0.99
(step
0.01)
Operating time (
t
CPhi2
<
def
)
0.04...100.0 s
0.04...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
—
Overvoltage - 59
Common configuration:
Voltage measurement type - phase-to phase/phase to neutral (
U
type59)
27
U
ph-ph
/
U
ph-n
Operating logic (
Logic
59) AND/OR
U> Element
Curve type (
U
>
Curve
)
DEFINITE/INVERSE
28
Note 27 With
U
ph-ph
setting all thresholds are in p.u.
U
n
;
with
U
ph-n
setting all thresholds are in p.u
E
n
Note 28 The mathematical formula for INVERSE curve is: t = (0.5 ∙
t
U
>
inv
) / [(
U
/
U
>
inv
) -
1
]
t:
operating time (in seconds)
t
U
>
inv
: operating time setting (referred to
U
/
U
>
inv
= 1.5 )
U:
input voltage
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021