TECHNICAL DATA
Trip threshold (
Dth
>)
0.800...1.500
Dq
B
(step 0.001
Dq
B
)
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
0.5% with 0.1
I
n
±
0.2% with 1
I
n
Operate time accuracy
5% ± 10 ms
—
Inadvertent energization - 50/27
I
UE
>
threshold
0.05...4.00
I
n
(step 0.01
I
n
)
U
UE
<
threshold
0.10...1.00
E
n
(step 0.01
E
n
)
Time delay trip
t
UE
>
0.0...10.0 s (step 0.1 s)
Reset time delay (
t
UE
-
RES
)
0.00...10.00 s (step 0.01 s)
Dropout ratio
0.95...0.98 (
I
UE
> threshold)
1.02...1.05(
U
UE
> threshold)
Reset time
≤
0.05 s
Overshoot time
0.03 s
Reference values
rest: 0 (
I
UE
> threshold)
rest: 1.2 (
U
UE
> threshold)
trip:
1.5
I
UE
> (
I
UE
> threshold)
trip:
0.8
U
UE
>(
U
UE
> threshold)
Pickup
accuracy ±
4% ±
1%
I
n
±
3% ±
0.05%
E
n
Operate
time
accuracy
5%
or
±
10 ms
—
Phase overcurrent - 50/51 side H
I
(H)
> Element
I
(H)
> Curve type (
I
(H)
>
Curve
) DEFINITE,
IEC/BS A, B, C, LIT, ANSI/IEEE MI, VI, EI
RECTIFIER,
I
2
t or EM
CLP operating mode (
I
(H)CLP>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
(H)CLP>
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
(H)
>
RES
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
First threshold definite time (
I
(H)
>
def
)
0.100...40.0
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...9.99
I
n
(step 0.01
I
nH
)
10.0...40.0
I
n
(step 0.1
I
nH
)
First threshold within CLP (
I
(H)CLP>def
)
0.100...40.0
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...9.99
I
n
(step 0.01
I
nH
)
10.0...40.0
I
n
(step 0.1
I
nH
)
Operating time (
t
(H)
>
def
)
0.04...200.00
s
0.04...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Inverse time
21
First threshold inverse time (
I
(H)
>
inv
)
0.100...20.00
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...20.00
I
n
(step 0.01
I
nH
)
First threshold
within CLP (
I
(H)CLP>inv
)
0.100...20.00
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...20.00
I
n
(step 0.01
I
nH
)
Operating time (
t
(H)
>
inv
)
0.02...60.0
s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
I
(H)
>> Element
Curve type (
I>>
Curve
)
DEFINITE
or
I
2
t
CLP operating mode (
I
(H)CLP
>>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
(H)CLP>>
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
(H)
>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Second threshold definite time (
I
(H)
>>
def
) 0.100...40.0
I
nH
0.100...0.999
I
n
(step 0.001
I
nH
)
1.00...9.99
I
n
(step 0.01
I
nH
)
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021