![Thytronic XMR-A 4l+1A Manual Download Page 226](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984226.webp)
226
FUNCTION CHARACTERISTICS
F_59-Char.ai
1.1
2
3
4
U
/
U
>inv
t
U
>
inv
= 100 s
t
U
>
inv
= 10 s
t
U
>
inv
= 1 s
t
U
>
inv
= 0.1 s
1.5
0.01
0.1
1
10
100
1000
10000
t
[s]
t
=
t
U
>inv
·
[(
U
/
U
>
inv
) - 1]
0.5
Inverse time operating characteristic concerning the first threshold (U>) of the overvoltage element - 59
Note: match of operating and setting time takes place when U/U>
inv
= 1.5
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021