Protection
IMx-M Manager
2 - 56
SKF Multilog O
n-Line System IMx-M
User Manual
Figure 2 - 34.
IMx-
M Manager Configuration O
verview.
For a fully equipped IMx-M rack, the configuration file of each slot contains the
following:
•
Slot 1: the configurations of CMM 1, PRM 1 and RLM 1
•
Slot 2: the configurations of CMM 2, PRM 2 and RLM 2
•
Slot 3: the configurations of CMM 3, PRM 3 and RLM 3
•
Slot 4: the configurations of CMM 4 and PRM 4.
Although only one master project file (*.mhf) is required per project (plant), because
condition monitoring and machine protection parts operate completely independently of
each other, two additional and distinct configuration files are created by the IMx-M
Manager for each slot within the rack.
•
Master Project File (*.mhf)
contains the hierarchy configuration of the project
(plant) and CMM comments of each channel.
•
Network Configuration File (*.imx)
contains the network configuration of a slot.
This network configuration file is downloaded to the CMM via its front panel (type 2)
USB connector.
•
Slot Configuration File (*.bin)
contains the machine protection configurations of a
slot (configuration of PRM and the associated RLM). This file is downloaded
separately to the protection module via its front panel (Mini B) USB connector.