Hardware
Protection Part Diagnostic Commands
4 - 34
SKF Multilog O
n-Line System IMx-M
User Manual
Protection Part Diagnostic Commands
Diagnostic commands are used to obtain information on various conditions of the IMx-
M system.
Diagnostic information will be available for the protection module to where the mini
USB cable is connected. Therefore, connect a mini USB cable to the protection module
for which various conditions will be checked.
Diagnostic commands can be performed by using the application tool IMx-M Manager
provided by @ptitude Observer DVD.
Set the Serial Communication to PRM Serial Interface and enter the following
commands manually on the Command area.
Important - It is strongly recommended to use the diagnostic interface in
disarmed mode only.
Table 4-13: Protection part diagnostic commands.
Command
Description
adc1
Status of internal power and the PRM internal temperature
Current circuit fault status (it is recommended to use "Send CF Command" via IMx-M
Manager's PRM Serial Commands)
cfguser
User configuration events by entering 8-character user name after the command
ch
Analog channel status
dumpcfg
Current user configuration (it is recommended to use "Get PRM Config from device" via
IMx-M Manager's PRM Serial Commands)
intd0
Current FW versions
in use by the PRM and RLM. Use this command to ensure all
slaves are running proper FW.
mb10
Modbus 1 (RS 485 connection L1) statistics
mb20
Modbus 2 (RS 485 connection L2) statistics
reboot
Reboot command
sver
FW version in use by the PRM and RLM. Thi
s shall only be used when the system is
disarmed.
ver
FW version information