Hardware
Hardware Configuration
4 - 16
SKF Multilog O
n-Line System IMx-M
User Manual
Analog Input Channel 1 to 8
Signal
Terminal
DIP A settings
Eddy probe
(–24 V)
–24 V
Signal
Com.
Shield
P
A
B
S
011000
Voltage source powered from the IMx
(max 30 mA)
+24 V
Signal
Com.
Shield
P
A
B
S
100100
4–
20 mA*
(IMx powered)
+ Signal
- Signal
N.C.
Shield
P
A
B
S
100101
N.C. = Not Connected
* All 4
–20 mA inputs have built-in internal 220
Ω
shunt resistor.
Figure 4 - 9.
Analog Input Channel 9-16 Front End.