Protection
Modbus
SKF Multilog On
-Line System IMx-M
2 - 183
User Manual
Analog Ch Alert/Danger Trigg Scale Factor and Value
Table 2-36: Analog ch alert/danger trigg scale factor & value.
Analog Ch Alert/Danger Trigg Scale Factor & Value
Bit 7-8
Scale factor for Low Alert Trigg level
Bit 5-6
Scale factor for High Alert Trigg level
Bit 3-4
Scale factor for Low Danger Trigg level
Bit 1-2
Scale factor for High Danger Trigg level
Bit representation:
00 = Not scaled (values multiplied by 1)
01 = Values multiplied by 10
10 = Values multiplied by 100
11 = Values multiplied by 1000
Analog Ch Trip Multiply Factor Definition
Table 2-37: Analog ch trip multiply factor definition.
Analog Ch Trip Multiply Factor Definition
High byte
used for Danger Trip Multiply
Low byte
used for Alert Trip Multiply
Value representation:
Value (between 10 and 250) is represented with one decimal, therefore 10 = 1.0 and
250 = 25.0.