Hardware
LED Indicators
4 - 32
SKF Multilog O
n-Line System IMx-M
User Manual
For a combined measurement type
Complementary Differential Expansion
consisting
of ch X and ch Y:
•
The individual analog ch X and Y cannot have any alarms set. The alarms are set to
the combined measurement channel.
•
If both ch X and ch Y are disarmed/circuit fault, then th
e combined measurement ch
status is disarmed/circuit fault.
•
If ch X or ch Y shows alert/danger, then the combined measurement ch status is
alert/danger.
Table 4-12: PRM LED indicators - Analog ch1 to ch16 for CDE combined measurement.
LED Indicator ANALOG ch1 to ch16 for Complementary Differential Expansion
Behavior (in priority
order, high to low)
Description
Off (10)
Channel not used for the moment
Value from this channel is not used for the moment (Decided by the defined
crossover voltage).
Current channel status is:
-
Analog ch is OK and Part of CDE but not used for the moment.
Note/Warning
: This is presented status. One channel may be out of its
sensor OK range, but that will not be presented until both channels are out of
their sensor OK range.
- Combination measurement ch status may be anything, depending on LED
on the other analog channel
Yellow fast flash (9)
Channel Channel Not OK/Alert/Danger
The analog channel is disarmed and the current channel status is:
- Combination measurement ch is disarmed and may also be any
combination of; alert, danger, danger first out, circuit fault (sensor not OK)
Green fast flash (8)
Channel Channel OK
The analog channel is disarmed and the current channel status is:
- Combination measurement
ch is OK and disarmed and may also be danger
first out
Toggle between green /
red / yellow (7)
Channel Circuit Fault (Not OK)
The current channel status is:
-
Both channels are in circuit fault (sensor not OK)
- Combination measurement ch is in circuit fa
ult (sensor not OK)
Red slow flash (6)
Channel Danger First Out
Current channel status is:
- Analog ch is used for the moment
- Combination measurement ch is alert, danger and danger first out
Red (5)
Channel Danger
Current channel status is:
- Analog ch is used for the moment
- Combination measurement ch is alert and danger