Protection
Modbus
SKF Multilog On
-Line System IMx-M
2 - 177
User Manual
Exported (Read) Modbus Registers
IMx-M item
Register
number(1)
Function
Data type
Min and Max
Dig Ch 1 Alert
High
1033
Digital Ch 1 Alert High trigg
level
Unsigned 16 bits
0 to 65 535
↓
↓
↓
Dig Ch 8 Alert
High
1040
Digital Ch 8 Alert High trigg
level
Dig Ch 1 Danger
Low
1073
Digital Ch 1 Danger Low
trigg level
Unsigned 16 bits
0 to 65 535
↓
↓
↓
Dig Ch 8 Danger
Low
1080
Digital Ch 8 Danger Low
trigg level
Dig Ch 1 Danger
High
1081
Digital Ch 1 Danger High
trigg level
Unsigned 16 bits
0 to 65 535
↓
↓
↓
Dig Ch 8 Danger
High
1088
Digital Ch 8 Danger High
trigg level
Analog Ch 1 Gap
Alert Low
1121
Analog Ch 1 Gap Alert Low
trigg level [mV]
Signed 16 bits
-32 768 to
+32 767
↓
↓
↓
Analog Ch 16
Gap Alert Low
1136
Analog Ch 16 Gap Alert
Low trigg level [mV]
Analog Ch 1 Gap
Alert High
1169
Analog Ch 1 Gap Alert High
trigg level [mV]
Signed 16 bits
-32 768 to
+32 767
↓
↓
↓
Analog Ch 16
Gap Alert High
1184
Analog Ch 16 Gap Alert
High trigg level [mV]
Analog Ch 1 Gap
Danger Low
1217
Analog Ch 1 Gap Danger
Low trigg level [mV]
Signed 16 bits
-32 768 to
+32 767
↓
↓
↓
Analog Ch 16
Gap Danger Low
1232
Analog Ch 16 Gap Danger
Low trigg level [mV]
Analog Ch 1 Gap
Danger High
1265
Analog Ch 1 Gap Danger
High trigg level [mV]
Signed 16 bits
-32 768 to
+32 767
↓
↓
↓
Analog Ch 16
Gap Danger High
1280
Analog Ch 16 Gap Danger
High trigg level [mV]