Hardware
LED Indicators
SKF Multilog On
-Line System IMx-M
4 - 31
User Manual
LED Indicator
Behavior
Description
ANALOG Ch1 to
Ch16*
Behavior listed in the
order of priority, high
to low (bigger # =
higher priority)
For Combined
Measurement type
CDE, see the separate
table, below.
Red (5)
Channel Danger
Current channel status is any combination of:
- Analog ch is Alert and Danger
- Gap is Danger
- Combination measurement ch is Alert and Danger
Yellow slow flash (4)
Channel Alert + Danger First Out
One of Analog ch, Gap or Combination measurement ch is
Danger First Out an
d current channel status is any
combination of:
- Analog ch is Alert
- Gap is Alert
- Combination measurement ch is Alert
Yellow (3)
Channel Alert
Current channel status is any combination of:
- Analog ch is Alert
- Gap is Alert
- Combination measurement ch is Alert
Green slow flash (2)
Channel OK + Danger First Out
One of Analog ch, Gap or Combination measurement ch is
Danger First Out and the current channel status is:
-
Analog ch is OK
-
Gap is OK
-
Combination measurement ch is OK
Green (1)
Channel OK
The current channel status is:
-
Analog ch is OK
-
Gap is OK
-
Combination measurement ch is OK
DIG/SPD Ch1 to Ch8
On
Digital input logic one.
Flash
Digital input toggle.
Off
Digital input logic zero.
RS485 Ch1 and Ch2
On/Flash
Communication indicator.
* Combined measurement types
Absolute Shaft Vibration
,
Piston Rod Drop XY (Average
and
Triggered)
and
Temperature Difference
consisting of ch X and ch Y:
•
If ch X is disarm/circuit fault and ch Y is armed, then ch Y LED shows status of ch Y
and combined measurement. See Disarm chapter.
•
If ch X is armed and ch Y is disarm/circuit fault, then ch X LED shows status of ch X
and combined measurement. See Disarm chapter.